Miscellaneous action | | | 4/16/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 3/19/2010 | 3/19/2010 | 3/19/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit approved for final status.
|
INSP-Alarm Testing | 3/18/2010 | 3/19/2010 | 3/19/2010 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed field testing.
|
Issue and Print Permit | | | 3/18/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/15/2010 | | 3/17/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
3/17/2010 07:34:35 SLC - activity updated through activity FIRA24 from case FIR10-00110.
|
Plan assigned to (Stephanie) | 3/16/2010 | | 3/17/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
3/17/2010 07:34:35 SLC - activity updated through activity FIRA24 from case FIR10-00110.
|
Alarm Plan Check | 3/17/2010 | | 3/17/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 3/17/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 3/17/2010 | | 3/17/2010 | | DONE |
|
|
|
|
Telephone call | | | 3/17/2010 | | DONE |
|
|
|
t/c w clint at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/17/2010 | | DONE |
|
|
|
|
1st review completed | | | 3/16/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 3/16/2010 | | 3/16/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 3/16/2010 | | DONE |
|
|
|
Spoke to Clint and explained I would need to deny the plans due to insufficient information to complete the review. I went over the following: The drawings are not 1/8" scale, I could not verify the spacing requirements for the notification has been met, the candela of the devices are not shown, devices are shown in areas that do not require notification and are not shown in areas that do require notification, the name of the designer and his/her qualification are not shown, etc.. He understood he would need to provide the information in the form of a resubmittal. I asked if he needed me to fax him anything formal indicating a resubmittal is required, and he stated he did not need anything further from me.
|
Plan resubmittals received | | | 3/16/2010 | | DONE |
|
|
|
|
Application received | | | 3/15/2010 | | |
|
|
|
|