Miscellaneous action | | | 6/7/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 4/26/2010 | 4/26/2010 | 4/26/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 4/23/2010 | 4/26/2010 | 4/26/2010 | A | PASS |
Forrest France
|
|
|
C/N items field verified for completion, final inspection passed.
|
INSP-Conference | 4/23/2010 | 4/23/2010 | 4/26/2010 | A | DONE |
Forrest France
|
|
|
Re permit status
|
Plan resubmittals received | | | 4/23/2010 | | |
Tisha Gallop
|
|
|
Plan modification: received two copies of application, data sheets and two 11" x 17" plan sheets; routed to fire review
|
Plan assigned to (Stephanie) | 4/23/2010 | | 4/23/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/23/2010 11:19:56 SLC - activity updated through activity FIRA24 from case FIR10-00124.
|
Alarm Plan Check | 4/23/2010 | | 4/23/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
plan modification (quick permit) approved (no written comments)
|
PLANS TAKEN FRONT DESK ALARM | | | 4/23/2010 | | DONE |
|
|
|
approved documents available at front counter
|
Inspection Record Card- Fire | 4/23/2010 | | 4/23/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/23/2010 | | DONE |
|
|
|
t/c w jay - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 4/23/2010 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 4/23/2010 | | |
Barbara Stitt
|
|
|
|
INSP-Alarm Testing | 4/19/2010 | 4/19/2010 | 4/19/2010 | P | PART |
Forrest France
|
|
|
New devices passed functional testing including the ID detector, antifreeze system tamper switches, OS&Y tampers at the double check, wet system flow switch and PIV tamper. Also tested the new area smoke detector and horn at the chemical storage room. Items needed for final include approved resubmittals showing the additional SD and horn at the chem. room, NFPA 72 record of completion report, legible labels at FACP for zone descriptors, repair the trouble conditon on the existing notification circut at the panel.
|
Issue and Print Permit | | | 4/7/2010 | | |
|
|
|
|
Plan assigned to (Stephanie) | 3/23/2010 | | 4/6/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/6/2010 09:59:38 SLC - activity updated through activity FIRA24 from case FIR10-00124.
|
Plan assigned to (Stephanie) | 3/23/2010 | | 4/6/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/6/2010 09:59:38 SLC - activity updated through activity FIRA24 from case FIR10-00124.
|
Alarm Plan Check | 4/6/2010 | | 4/6/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
quick permit approved - no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/6/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 4/6/2010 | | 4/6/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/6/2010 | | DONE |
|
|
|
t/w w jay at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/6/2010 | | DONE |
|
|
|
|
Miscellaneous action | | | 4/5/2010 | | DONE |
|
|
|
Recieved appropriate documentation from contractor
|
1st review completed | | | 3/25/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 3/25/2010 | | 3/25/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Approval pending receipt of letter from engineer.
|
Miscellaneous action | | | 3/25/2010 | | DONE |
|
|
|
email received from Rob at Protex stating there are three existing available zones and that zone 3 shall be used for the new induct detector.
|
Telephone call | | | 3/23/2010 | | DONE |
|
|
|
Spoke to Rob and asked him to please email or fax me the following information and reference permit # FIR10-00124:
-A letter from the engineer stating he has reviewed the plans (or received and approved verbal notification of the drawings being submitted) and they meet the design intent.
-A statement indicating the available zones on the existing FACP.
|
Application received | | | 3/23/2010 | | |
|
|
|
|