Miscellaneous action | | | 11/14/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 8/30/2011 | 9/1/2011 | 9/1/2011 | A | PASS |
Forrest France
|
|
|
Noted correction items finished. Fire alarm permit finaled.
|
INSP-Final Inspection | 7/29/2011 | 7/29/2011 | 7/29/2011 | P | PART |
Forrest France
|
|
|
Remainder of correction items include; repair one non-functional H/S at the womens locker room sauna, repair notification device at the first floor family restroom, adjust cd setting at one appliance in the basement level womens locker room. Need to verify EOL voltage and reverify notification functionality at the cardio area.
|
INSP-Conference | 7/27/2011 | 7/27/2011 | 7/27/2011 | A | DONE |
Forrest France
|
|
|
Zach phone #: ###-#### Regarding corrections and final inspection schedule.
|
INSP-Final Inspection | 7/20/2011 | 7/21/2011 | 7/22/2011 | A | FAIL |
Forrest France
|
|
|
Items noted during notification circut testing include sync issues at the basement level, various non-functional devices on the 1st floor, insufficient EOL voltage as measured, missing tone cycle preceeding and following the voice message, audibility at some areas such as the gym, spin, fitness, cardio and weight rooms do not appear sufficient.
|
INSP-Alarm Testing | 7/11/2011 | 7/11/2011 | 7/11/2011 | A | PART |
Forrest France
|
|
|
Ref. stamped plan set for annotations regarding devices tested to date.
|
INSP-Alarm Testing | 7/7/2011 | 7/7/2011 | 7/8/2011 | P | PART |
Forrest France
|
|
|
Completed elevator device testing, SD at nac's and FACP, reviewed changes and adjustments to date, discussed items remaining including AC power light at the panel, guards at gym appliances, signage at doors to the FACP, as-builts/map, and notification testing schedule.
|
INSP-Alarm Testing | 6/27/2011 | 6/28/2011 | 6/28/2011 | A | PART |
Forrest France
|
|
|
MP stations tested satisfactory.
|
INSP-Alarm Testing | 6/27/2011 | 6/27/2011 | 6/28/2011 | A | PART |
Forrest France
|
|
|
Remainder of duct detectors tested okay.
|
INSP-Final Inspection | 6/20/2011 | 6/23/2011 | 6/24/2011 | P | PART |
Forrest France
|
|
|
Completed testing of ID and DD at the first, second and third floors.
|
INSP-Conference | 6/6/2011 | 6/6/2011 | 6/6/2011 | P | DONE |
Forrest France
|
|
|
Regarding inspection schedule.
|
INSP-Alarm Testing | 5/25/2011 | 5/26/2011 | 5/26/2011 | A | PART |
Forrest France
|
|
|
Completed testing of ID and DD devices at the basement levels. Noted tamper valve at the elevator machine room to be monitored, as-builts to reflect deleted and added devices, dampers have been repaired and verified for functionality. Previously noted correction items underway, some are finished. Ref. plan set for annotations.
|
INSP-Alarm Testing | 5/25/2011 | 5/25/2011 | 5/25/2011 | A | PART |
Forrest France
|
|
|
|
INSP-Alarm Testing | 5/4/2011 | 5/6/2011 | 5/6/2011 | A | PART |
Forrest France
|
|
|
Issues noted today include DD trouble which supercedes supervisory condition for unit shutdown, non-latching ID smoke detectors, dampers at some basement ducts are not functional including L2S019 and L2S020, TS at the sprinkler riser are latching," AC power on" lamp at the panel remains illuminated during power off condition.
|
INSP-Final Inspection | 4/27/2011 | 4/28/2011 | 4/28/2011 | A | DEFR |
Forrest France
|
|
|
Request between 9a.m. & 10 a.m.----Earl Phone #: ###-####
|
FIR-Aging Inspection | 4/14/2011 | 4/14/2011 | 4/14/2011 | A | PEND |
Forrest France
|
|
|
Work in progress, per contractor one duct detector remains.
|
FIR-Aging Inspection | 3/16/2011 | 3/16/2011 | 3/18/2011 | | DONE |
Forrest France
|
|
|
In progress
|
FIR-Aging Inspection | 1/12/2011 | 1/12/2011 | 1/12/2011 | | DONE |
Forrest France
|
|
|
Site work in progress
|
INSP-Conference | 11/10/2010 | 11/12/2010 | 11/12/2010 | A | DONE |
Forrest France
|
|
|
On site conference with contractor regarding notification appliance locations at the climbing wall room and the rooftop playground area- plan modification to show revised locations. Also discussed protocol for new system transfer, demo work, new monitoring and impairments.
|
FIR-Aging Inspection | 9/3/2010 | 9/3/2010 | 9/3/2010 | | DONE |
Forrest France
|
|
|
Work in progress.
|
CHANGE STATUS TO (ISS) | | | 9/2/2010 | | |
|
|
|
|
(F) Reprint permit | | | 9/2/2010 | | |
|
|
|
|
Alarm Plan Check | 6/2/2010 | | 6/2/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved. see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 6/2/2010 | | DONE |
|
|
|
Approved plan modification documents available at front counter
|
Inspection Record Card- Fire | 6/2/2010 | | 6/2/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/2/2010 | | DONE |
|
|
|
t/c w john at ###-#### - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 6/2/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/24/2010 | | |
Stephanie L. Cobbley
|
|
|
rec'd 2 sets
|
Issue and Print Permit | | | 5/17/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 3/29/2010 | | 5/14/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
5/14/2010 14:27:49 SLC - activity updated through activity FIRA24 from case FIR10-00137.
|
Plan assigned to (Stephanie) | | | 5/14/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
5/14/2010 14:27:49 SLC - activity updated through activity FIRA24 from case FIR10-00137.
|
Alarm Plan Check | 5/14/2010 | | 5/14/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments and redlined plans
|
PLANS TAKEN FRONT DESK ALARM | | | 5/14/2010 | | DONE |
|
|
|
approved redlined plans available at front counter
|
Inspection Record Card- Fire | 5/14/2010 | | 5/14/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/14/2010 | | DONE |
|
|
|
t/c w john at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/14/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/10/2010 | | |
Stephanie L. Cobbley
|
|
|
rec'd 2 sets
|
Alarm Plan Check | 4/30/2010 | | 4/30/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied. See review comments and redlines
|
Telephone call | | | 4/30/2010 | | DONE |
|
|
|
Called John to let him know the plans would need to be denied.
|
Miscellaneous action | | | 4/30/2010 | | DONE |
|
|
|
faxed review comments to Fire Sentry Systems
|
Miscellaneous action | | | 4/30/2010 | | DONE |
|
|
|
Placed denied plans up front for customer retrieval.
|
Plan resubmittals received | | | 4/26/2010 | | |
Tisha Gallop
|
|
|
recevied application, three folders of submittal info and three new sets of plans; routed to Fire review
|
1st review completed | | | 4/6/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 4/6/2010 | | 4/6/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans failed - design is for horn/strobes, however the 'A' occupancy areas exceed 1000 occupant load and require voice evacuation. no written review done because a sufficient review can not be completed with the submitted information.
|
Telephone call | | | 4/6/2010 | | DONE |
|
|
|
Spoke to John L. with Fire Sentry and let him know the plans are denied, but there are no review comments. I offered to copy the architectural summary we have that shows the occupant loads. He asked that I put that with the denied plans up front.
|
Miscellaneous action | | | 4/6/2010 | | DONE |
|
|
|
copied architectural summary from our records that indicate the occupancy types and their loads and placed them with the denied plans up at the front counter.
|
Telephone call | | | 4/2/2010 | | DONE |
|
|
|
Spoke to John to let him know the city records indicate the A areas of the building exceed 1000 occupant load and that he would need to resubmit the plans showing a voice evacuation system included in the fire alarm. He is going to come in next week to go over the information I have. I am going to wait to fail the plans until after that meeting in case something comes to light that overrides the information we have on file.
|
Application received | | | 3/29/2010 | | |
|
|
|
|
INSP-Final Inspection | 5/2/2011 | 5/3/2011 | | A | |
Forrest France
|
|
|
EARL Phone #: ###-####
|