Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberFIR10-00137
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1050 W STATE ST
Project NameYMCA-FIRE ALARM SYSTEM REPLACE
Customer Number 
ePlanReview 
Description
6-2-10: PLAN MODIFICATION
This plan modification is to provide additional in-duct detectors instead of open area detection, therefore all fire/smoke dampers will be shut down using in-duct detectors. This plan modification also includes incorporating previous redlines and review comments from the review dated 5/14/10.

5-14-10: This fire alarm permit is to replace the existing fire alarm panel and all components. This includes bringing the entire building up to meet current IFC and NFPA requirements. A manual system with full voice evacuation for notification, duct detectors for HVAC shutdown, elevator recall, and sprinkler system monitoring. There are also areas where smoke detectors are used in lieu of in-duct detectors to shut down fire/smoke dampers, but some of the dampers are shut down using in-duct detectors due to existing motor controls that are being left alone. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  11/14/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection8/30/20119/1/20119/1/2011APASS
DetailsForrest France
Noted correction items finished. Fire alarm permit finaled.
INSP-Final Inspection7/29/20117/29/20117/29/2011PPART
DetailsForrest France
Remainder of correction items include; repair one non-functional H/S at the womens locker room sauna, repair notification device at the first floor family restroom, adjust cd setting at one appliance in the basement level womens locker room. Need to verify EOL voltage and reverify notification functionality at the cardio area.
INSP-Conference7/27/20117/27/20117/27/2011ADONE
DetailsForrest France
Zach phone #: ###-#### Regarding corrections and final inspection schedule.
INSP-Final Inspection7/20/20117/21/20117/22/2011AFAIL
DetailsForrest France
Items noted during notification circut testing include sync issues at the basement level, various non-functional devices on the 1st floor, insufficient EOL voltage as measured, missing tone cycle preceeding and following the voice message, audibility at some areas such as the gym, spin, fitness, cardio and weight rooms do not appear sufficient.
INSP-Alarm Testing7/11/20117/11/20117/11/2011APART
DetailsForrest France
Ref. stamped plan set for annotations regarding devices tested to date.
INSP-Alarm Testing7/7/20117/7/20117/8/2011PPART
DetailsForrest France
Completed elevator device testing, SD at nac's and FACP, reviewed changes and adjustments to date, discussed items remaining including AC power light at the panel, guards at gym appliances, signage at doors to the FACP, as-builts/map, and notification testing schedule.
INSP-Alarm Testing6/27/20116/28/20116/28/2011APART
DetailsForrest France
MP stations tested satisfactory.
INSP-Alarm Testing6/27/20116/27/20116/28/2011APART
DetailsForrest France
Remainder of duct detectors tested okay.
INSP-Final Inspection6/20/20116/23/20116/24/2011PPART
DetailsForrest France
Completed testing of ID and DD at the first, second and third floors.
INSP-Conference6/6/20116/6/20116/6/2011PDONE
DetailsForrest France
Regarding inspection schedule.
INSP-Alarm Testing5/25/20115/26/20115/26/2011APART
DetailsForrest France
Completed testing of ID and DD devices at the basement levels. Noted tamper valve at the elevator machine room to be monitored, as-builts to reflect deleted and added devices, dampers have been repaired and verified for functionality. Previously noted correction items underway, some are finished. Ref. plan set for annotations.
INSP-Alarm Testing5/25/20115/25/20115/25/2011APART
DetailsForrest France
INSP-Alarm Testing5/4/20115/6/20115/6/2011APART
DetailsForrest France
Issues noted today include DD trouble which supercedes supervisory condition for unit shutdown, non-latching ID smoke detectors, dampers at some basement ducts are not functional including L2S019 and L2S020, TS at the sprinkler riser are latching," AC power on" lamp at the panel remains illuminated during power off condition.
INSP-Final Inspection4/27/20114/28/20114/28/2011ADEFR
DetailsForrest France
Request between 9a.m. & 10 a.m.----Earl Phone #: ###-####
FIR-Aging Inspection4/14/20114/14/20114/14/2011APEND
DetailsForrest France
Work in progress, per contractor one duct detector remains.
FIR-Aging Inspection3/16/20113/16/20113/18/2011 DONE
DetailsForrest France
In progress
FIR-Aging Inspection1/12/20111/12/20111/12/2011 DONE
DetailsForrest France
Site work in progress
INSP-Conference11/10/201011/12/201011/12/2010ADONE
DetailsForrest France
On site conference with contractor regarding notification appliance locations at the climbing wall room and the rooftop playground area- plan modification to show revised locations. Also discussed protocol for new system transfer, demo work, new monitoring and impairments.
FIR-Aging Inspection9/3/20109/3/20109/3/2010 DONE
DetailsForrest France
Work in progress.
CHANGE STATUS TO (ISS)  9/2/2010  
(F) Reprint permit  9/2/2010  
Alarm Plan Check6/2/2010 6/2/2010 PASS
DetailsStephanie L. Cobbley
Plan modification approved. see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  6/2/2010 DONE
Approved plan modification documents available at front counter
Inspection Record Card- Fire6/2/2010 6/2/2010 DONE
DetailsPatricia Smith
Telephone call  6/2/2010 DONE
t/c w john at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  6/2/2010 DONE
Details
Plan resubmittals received  5/24/2010  
DetailsStephanie L. Cobbley
rec'd 2 sets
Issue and Print Permit  5/17/2010 DONE
Plan assigned to (Stephanie)3/29/2010 5/14/2010 DONE
DetailsStephanie L. Cobbley
5/14/2010 14:27:49 SLC - activity updated through activity FIRA24 from case FIR10-00137.
Plan assigned to (Stephanie)  5/14/2010 DONE
DetailsStephanie L. Cobbley
5/14/2010 14:27:49 SLC - activity updated through activity FIRA24 from case FIR10-00137.
Alarm Plan Check5/14/2010 5/14/2010 PASS
DetailsStephanie L. Cobbley
see review comments and redlined plans
PLANS TAKEN FRONT DESK ALARM  5/14/2010 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire5/14/2010 5/14/2010 DONE
DetailsPatricia Smith
Telephone call  5/14/2010 DONE
t/c w john at ###-#### - permit ready and fees given
Permit Ready to Issue  5/14/2010 DONE
Details
Plan resubmittals received  5/10/2010  
DetailsStephanie L. Cobbley
rec'd 2 sets
Alarm Plan Check4/30/2010 4/30/2010 FAIL
DetailsStephanie L. Cobbley
Plans denied. See review comments and redlines
Telephone call  4/30/2010 DONE
Called John to let him know the plans would need to be denied.
Miscellaneous action  4/30/2010 DONE
faxed review comments to Fire Sentry Systems
Miscellaneous action  4/30/2010 DONE
Placed denied plans up front for customer retrieval.
Plan resubmittals received  4/26/2010  
DetailsTisha Gallop
recevied application, three folders of submittal info and three new sets of plans; routed to Fire review
1st review completed  4/6/2010 DONE
Alarm Plan Check4/6/2010 4/6/2010 FAIL
DetailsStephanie L. Cobbley
Plans failed - design is for horn/strobes, however the 'A' occupancy areas exceed 1000 occupant load and require voice evacuation. no written review done because a sufficient review can not be completed with the submitted information.
Telephone call  4/6/2010 DONE
Spoke to John L. with Fire Sentry and let him know the plans are denied, but there are no review comments. I offered to copy the architectural summary we have that shows the occupant loads. He asked that I put that with the denied plans up front.
Miscellaneous action  4/6/2010 DONE
copied architectural summary from our records that indicate the occupancy types and their loads and placed them with the denied plans up at the front counter.
Telephone call  4/2/2010 DONE
Spoke to John to let him know the city records indicate the A areas of the building exceed 1000 occupant load and that he would need to resubmit the plans showing a voice evacuation system included in the fire alarm. He is going to come in next week to go over the information I have. I am going to wait to fail the plans until after that meeting in case something comes to light that overrides the information we have on file.
Application received  3/29/2010  
INSP-Final Inspection5/2/20115/3/2011 A 
DetailsForrest France
EARL Phone #: ###-####