Miscellaneous action | | | 9/8/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 7/22/2010 | 7/23/2010 | 7/23/2010 | A | PASS |
Forrest France
|
|
|
Correction notice items are finished, final walkthrough passed. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/22/2010 | 7/22/2010 | 7/22/2010 | P | FAIL |
Troy Cobbley
|
|
|
A different backflow preventor and water meter have been installed than what was submitted. The hydraulic calculations have been re-approved by tim. Several pendant heads are installed too close to surface mounted light fixtures. They need to be a minumum 3'-6" away. Several pendants also appear to be too close to ceiling fans. They need to be atleast 36" away or meet one of the exceptions. The riser service tag, head box, flow through correct orfice, removing/locking of handles were not verified.
|
INSP-Conference | 4/7/2010 | 4/7/2010 | 4/7/2010 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Tim Frost and he and the code are ok with the area that was previously shown to be a sprinklered storage room now being a unsprinklered exterior patio.
|
INSP-Sprinkler Rough-in | 4/6/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Troy Cobbley
|
|
|
The overspaced sprinkler pendants have been corrected. Sprinkler piping is ok to cover.
|
INSP-Sprinkler Rough-in | 4/5/2010 | 4/6/2010 | 4/6/2010 | A | FAIL |
Troy Cobbley
|
|
|
Four pendant heads exceed the maximum calculated of 8' off of walls. Also the underground sprinkler piping is poly plastic not copper as per the drawings. Also the area marked "Storage" is now an exterior covered patio with the sprinkler protection deleted.
|
Issue and Print Permit | | | 4/5/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 3/30/2010 | | 3/31/2010 | | DONE |
Tim Frost
|
|
|
3/31/2010 13:39:43 TRF - activity updated through activity FIRA22 from case FIR10-00141.
|
Plan resubmittals received | | | 3/31/2010 | | |
Tim Frost
|
|
|
rec'd 3 sets
|
Sprinkler Plan Check | 3/31/2010 | | 3/31/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/31/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 3/31/2010 | | 3/31/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 3/31/2010 | | DONE |
|
|
|
t/c w vanessa at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/31/2010 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/30/2010 | | 3/30/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 3/30/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 3/30/2010 | | DONE |
|
|
|
Emailed comments
|
Telephone call | | | 3/30/2010 | | DONE |
|
|
|
t/c w vanessa at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 3/30/2010 | | |
|
|
|
|