Miscellaneous action | | | 4/16/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 4/14/2010 | 4/15/2010 | 4/15/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Issue and Print Permit | | | 4/13/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/6/2010 | | 4/8/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/8/2010 07:40:13 SLC - activity updated through activity FIRA24 from case FIR10-00150.
|
Plan assigned to (Stephanie) | 4/6/2010 | | 4/8/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/8/2010 07:40:13 SLC - activity updated through activity FIRA24 from case FIR10-00150.
|
1st review completed | | | 4/8/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 4/8/2010 | | 4/8/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
quick permit passed - no written review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/8/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 4/8/2010 | | 4/8/2010 | | DONE |
|
|
|
|
Telephone call | | | 4/8/2010 | | DONE |
|
|
|
t/c w ken at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/8/2010 | | DONE |
|
|
|
|
Application received | | | 4/6/2010 | | |
|
|
|
|