Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 7/8/2010 | 7/8/2010 | 7/8/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 5/26/2010 | 5/27/2010 | 5/27/2010 | A | PASS |
Troy Cobbley
|
|
|
The wood bracing has been covered with dry wall. The items have been corrected. The sprinkler piping can be covered.
|
INSP-Sprinkler Rough-in | 5/24/2010 | 5/24/2010 | 5/24/2010 | P | PART |
Troy Cobbley
|
|
|
There are two locations where there are two sprinkler pendants piped from the same 1" outlet which is not allowed. One pendant was missed being plunged and another exceeds 9' off of the single wall allowed. Also there are four rooms where wood framing/beams have been installed above the ceilings which can be covered with dry wall or replaced with fire treated wood. I discussed this with Don and Matt. Ceiling tile can be installed everywhere except these four rooms.
|
Issue and Print Permit | | | 5/18/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 4/7/2010 | | 4/12/2010 | | DONE |
Tim Frost
|
|
|
4/12/2010 08:42:30 TRF - activity updated through activity FIRA22 from case FIR10-00155.
|
Sprinkler Plan Check | 4/12/2010 | | 4/12/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/12/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 4/12/2010 | | 4/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/12/2010 | | DONE |
|
|
|
left vm for don at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/12/2010 | | DONE |
|
|
|
|
Telephone call | | | 4/9/2010 | | DONE |
|
|
|
t/c w don at ###-#### - permit denied - needs to be picked up and resubmitted
|
Plan resubmittals received | | | 4/9/2010 | | |
Tim Frost
|
|
|
rec'd 2 sets
|
Sprinkler Plan Check | 4/8/2010 | | 4/8/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 4/8/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 4/8/2010 | | DONE |
|
|
|
Emailed comments
|
Application received | | | 4/7/2010 | | |
|
|
|
|