Miscellaneous action | | | 12/2/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/4/2010 | 11/4/2010 | 11/5/2010 | P | PASS |
Forrest France
|
|
|
Noted correction item field verified, fire alarm permit okayed for final status.
|
INSP-Final Inspection | 9/1/2010 | 9/2/2010 | 9/2/2010 | A | FAIL |
Troy Cobbley
|
|
|
Everything is ok except a module needs to be added so that when a battery is disconnected a trouble signal is received. All other signals were verified.
|
FIR-Aging Inspection | 8/10/2010 | 8/10/2010 | 8/12/2010 | | NR |
Troy Cobbley
|
|
|
Per Tim this will be scheduled for next week
|
Issue and Print Permit | | | 5/11/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/9/2010 | | 4/14/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/14/2010 11:42:23 SLC - activity updated through activity FIRA24 from case FIR10-00158.
|
1st review completed | | | 4/14/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 4/14/2010 | | 4/14/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/14/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 4/14/2010 | | 4/14/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/14/2010 | | DONE |
|
|
|
t/c w lisa at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/14/2010 | | DONE |
|
|
|
|
Telephone call | | | 4/13/2010 | | DONE |
|
|
|
Left a third message for Tim letting him know that if I did not hear from him by the end of today regarding the additional information I requested, that I would need to fail the plans.
|
Miscellaneous action | | | 4/13/2010 | | DONE |
|
|
|
Recieved requested information
|
Telephone call | | | 4/12/2010 | | DONE |
|
|
|
I left two messages for Tim Ezell at Crane Alarm (one at 9am and one at 3pm). The submittals did not have the data sheet for the IntelliTap, did not have the correct battery data sheet (needs at least a 7.5 per the panel data sheet and only a 7ah was provided), and the Permit Application had not been completely filled out.
|
Application received | | | 4/9/2010 | | |
|
|
|
|