Miscellaneous action | | | 2/8/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 12/21/2010 | 12/21/2010 | 12/21/2010 | P | PASS |
Forrest France
|
|
|
Corrections verified, fire alarm permit finaled.
|
INSP-Final Inspection | 12/16/2010 | 12/16/2010 | 12/17/2010 | P | NH |
Forrest France
|
|
|
|
INSP-Final Inspection | 12/15/2010 | 12/16/2010 | 12/16/2010 | A | FAIL |
Forrest France
|
|
|
Still need revised account information- supervisory signals were not recieved by central station monitoring.
|
INSP-Final Inspection | 12/13/2010 | 12/13/2010 | 12/14/2010 | P | CANC |
Forrest France
|
|
|
Insufficient netcon rating.
|
INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 | A | FAIL |
Forrest France
|
|
|
Account information at central station needs revised to match signals sent. All points reported as "3rd floor RTU".
|
INSP-Final Inspection | 11/8/2010 | 11/8/2010 | 11/8/2010 | P | PART |
Forrest France
|
|
|
NAC circut testing scheduled 11/9, supervisory signals okay.
|
INSP-Final Inspection | 11/5/2010 | 11/5/2010 | 11/5/2010 | P | NR |
Forrest France
|
|
|
Tim Phone #: ###-####
|
FIR-Aging Inspection | 8/10/2010 | 8/10/2010 | 8/10/2010 | | DONE |
Forrest France
|
|
|
Pending site inspection request by contractor.
|
Issue and Print Permit | | | 5/11/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/9/2010 | | 4/14/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
4/14/2010 15:05:31 SLC - activity updated through activity FIRA24 from case FIR10-00164.
|
1st review completed | | | 4/14/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 4/14/2010 | | 4/14/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/14/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 4/14/2010 | | 4/14/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/14/2010 | | DONE |
|
|
|
t/c w lisa at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/14/2010 | | DONE |
|
|
|
|
Telephone call | | | 4/13/2010 | | DONE |
|
|
|
Left a third message for Tim letting him know that if I did not hear from him by the end of today regarding the additional information I requested, that I would need to fail the plans.
|
Miscellaneous action | | | 4/13/2010 | | DONE |
|
|
|
Recieved requested information
|
Telephone call | | | 4/12/2010 | | DONE |
|
|
|
I left two messages for Tim Ezell at Crane Alarm (one at 9am and one at 3pm). The submittals did not have the data sheet for the IntelliTap, did not have the correct battery data sheet (needs at least a 7.5 per the panel data sheet and only a 7ah was provided), and the Permit Application had not been completely filled out.
|
Application received | | | 4/9/2010 | | |
|
|
|
|