Permit NumberFIR10-00193
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 7800 W USTICK RD
Project NameBAY POINT DENTAL
Customer Number 
ePlanReview 
Description
This fire alarm permit is to re-circuit existing zones on the existing fire alarm panel to provide a spare zone for two new tamper switches. Notification is not part of this permit scope of work. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/3/20106/7/20106/7/2010APASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  6/7/2010 DONE
Plans taken to records for scanning.
Issue and Print Permit  5/26/2010 DONE
Inspection Record Card- Fire5/21/2010 5/21/2010 DONE
DetailsPatricia Smith
Telephone call  5/21/2010 DONE
left vm for dave at ###-#### - permit ready and fees given
Permit Ready to Issue  5/21/2010 DONE
Details
Plan assigned to (Stephanie)4/27/2010 5/20/2010 DONE
DetailsStephanie L. Cobbley
5/20/2010 15:18:04 SLC - activity updated through activity FIRA24 from case FIR10-00193.
Alarm Plan Check5/20/2010 5/20/2010 PASS
DetailsStephanie L. Cobbley
see review comments
PLANS TAKEN FRONT DESK ALARM  5/20/2010 DONE
approved plans available at front counter
Plan resubmittals received  5/14/2010  
DetailsTisha Gallop
received two copies of application, submittal folders and drawings; taken to fire review
1st review completed  4/28/2010 DONE
Alarm Plan Check4/28/2010 4/28/2010 FAIL
DetailsStephanie L. Cobbley
Not approved. The tampers have been shown on the same zone as a bell supervision module that is located at the opposite end of the building. This is not allowed due to code requiring distinct signals for devices. The bell supervision module cannot be allowed to be confused with the sprinkler tamper switches. Resubmittal required. No written comments.
Telephone call  4/28/2010 DONE
Spoke with Dave Whiting to let him know the plans are denied, and that the tamper switches cannot go on the same zone as the bell supervision module located on the opposite end of the building. He indicated he would recircuit some of the devices. I let him know that the resubmittal would not be allowed to be a quick permit if new circuits/zones or re-circuiting is involved. He stated he understood.
Application received  4/27/2010