INSP-Final Inspection | 6/3/2010 | 6/7/2010 | 6/7/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
Miscellaneous action | | | 6/7/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
Issue and Print Permit | | | 5/26/2010 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/21/2010 | | 5/21/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/21/2010 | | DONE |
|
|
|
left vm for dave at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/21/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 4/27/2010 | | 5/20/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
5/20/2010 15:18:04 SLC - activity updated through activity FIRA24 from case FIR10-00193.
|
Alarm Plan Check | 5/20/2010 | | 5/20/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/20/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Plan resubmittals received | | | 5/14/2010 | | |
Tisha Gallop
|
|
|
received two copies of application, submittal folders and drawings; taken to fire review
|
1st review completed | | | 4/28/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 4/28/2010 | | 4/28/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Not approved. The tampers have been shown on the same zone as a bell supervision module that is located at the opposite end of the building. This is not allowed due to code requiring distinct signals for devices. The bell supervision module cannot be allowed to be confused with the sprinkler tamper switches. Resubmittal required. No written comments.
|
Telephone call | | | 4/28/2010 | | DONE |
|
|
|
Spoke with Dave Whiting to let him know the plans are denied, and that the tamper switches cannot go on the same zone as the bell supervision module located on the opposite end of the building. He indicated he would recircuit some of the devices. I let him know that the resubmittal would not be allowed to be a quick permit if new circuits/zones or re-circuiting is involved. He stated he understood.
|
Application received | | | 4/27/2010 | | |
|
|
|
|