Miscellaneous action | | | 9/8/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 8/9/2010 | 8/10/2010 | 8/10/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 | P | FAIL |
Troy Cobbley
|
|
|
There is a pendant head located in a basement closet that has been installed under 4" from a wall. I contacted Tim about the garage door in the basement storage room that is obstructing a single pendant head. Tim stated that he was alright with it.
|
INSP-Sprinkler Rough-in | 5/13/2010 | 5/14/2010 | 5/14/2010 | P | DONE |
Troy Cobbley
|
|
|
Rough In Passed. The GC said he would put batt insulation over the piping first,over the visqueen and then the blow insulation.
Raul is the contact. Thanks Inspection requested from web by: Stan Beus Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 5/12/2010 | 5/13/2010 | 5/13/2010 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for deficiencies that need corrected. This includes overspaced pendants and tenting/insulation issues.
|
Issue and Print Permit | | | 4/29/2010 | | DONE |
|
|
|
|
Application received | | | 4/28/2010 | | |
|
|
|
|
Pending Assignment by SAM | 4/28/2010 | | 4/28/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
4/28/2010 14:22:56 ALR - activity updated through activity FIRA158 from case FIR10-00196.
|
Plan assigned to (Tim) | 4/28/2010 | | 4/28/2010 | | DONE |
Tim Frost
|
|
|
4/28/2010 15:50:22 TRF - activity updated through activity FIRA22 from case FIR10-00196.
|
Sprinkler Plan Check | 4/28/2010 | | 4/28/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 4/28/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/28/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 4/28/2010 | | 4/28/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/28/2010 | | DONE |
|
|
|
left vm for cameron at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/28/2010 | | DONE |
|
|
|
|