INSP-Final Inspection | 10/15/2018 | 10/16/2018 | 10/16/2018 | P | PASS |
Jim Page
|
|
|
Fire sprinkler tampers were not required for the size of the sprinkler system at time of install, PIV is locked in the open position and flow switch is monitored, final inspection for scope of work complete.
Ray McQueen, inspecting technician, building access limited to 1200 - 1500 10/16 Phone #: ###-#### Inspection requested via web by Rose Peterson
|
(F) Reprint permit | | | 9/11/2018 | | DONE |
|
|
|
|
Miscellaneous action | | | 9/10/2018 | | DONE |
|
|
|
Emailed Rose Peterson to see if the final acceptace test (monitor PIV) can be completed soon.
|
FIR-Aging Inspection | 9/26/2013 | 9/26/2013 | 9/26/2013 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 2/28/2013 | 2/28/2013 | 2/28/2013 | | PEND |
Forrest France
|
|
|
Final pending PIV monitor
|
FIR-Aging Inspection | 11/29/2012 | 11/29/2012 | 11/29/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 8/30/2012 | 8/30/2012 | 8/31/2012 | | DEFR |
Forrest France
|
|
|
|
FIR-Aging Inspection | 5/31/2012 | 5/31/2012 | 6/1/2012 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/22/2011 | 11/22/2011 | 11/22/2011 | | PART |
Forrest France
|
|
|
Final pending tamper switch at the PIV.
|
FIR-Aging Inspection | 7/21/2011 | 7/21/2011 | 7/21/2011 | | PEND |
Forrest France
|
|
|
Ref. activity note 7/8
|
Telephone call | | | 7/8/2011 | | DONE |
|
|
|
Spoke with Bret Anderson regarding the status of the project. He said that he is working with the owner to get the PIV replaced. Work is in progress.
|
FIR-Aging Inspection | 3/17/2011 | 3/17/2011 | 3/18/2011 | | PEND |
Forrest France
|
|
|
|
FIR-Aging Inspection | 1/6/2011 | 1/6/2011 | 1/10/2011 | | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 | A | PART |
Forrest France
|
|
|
See activity notes 5/20.
|
INSP-Final Inspection | 5/18/2010 | 5/20/2010 | 5/20/2010 | A | FAIL |
Forrest France
|
|
|
Post indicator valve must be electronically supervised per IFC requirements. Approved plans also indicate a tamper switch at the PIV- final pending corrections. Remiander of work tested satisfactory, netcon rated 5 at the time of inspection.
|
Issue and Print Permit | | | 5/13/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/5/2010 | | 5/12/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
5/12/2010 09:22:15 SLC - activity updated through activity FIRA24 from case FIR10-00213.
|
1st review completed | | | 5/12/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 5/12/2010 | | 5/12/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/12/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 5/12/2010 | | 5/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/12/2010 | | DONE |
|
|
|
left vm for bret at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/12/2010 | | DONE |
|
|
|
|
Application received | | | 5/5/2010 | | |
|
|
|
|
INSP-Final Inspection | 9/10/2018 | 9/11/2018 | | A | |
Lee G Meredith
|
|
|
Building access is open, inspecting technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson
|