Permit Information
Permit NumberFIR10-00238
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 7225 W BETHEL ST
Project Name7225 Bethel
Customer Number 
ePlanReview 
Description
Fire Work Scope:

The Fire Sprinkler Scope of work consists of extending an existing wet pipe gridded sprinkler system. The existing system is supplied by 8" C-900 underground piping, 8" backflow preventer, 8" riser and 8" feed main. The primary and secondary mains are both entirely 6" pipe. The existing branch lines are 3" pipe and the new branch lines will be 2½" pipe. The area under this permit will be storing group A plastic on wood pallets, no shelves, on racks to a maximum of 25' high. ESFR sprinklers will be utilized to protect this storage. The racks will be storing Coca products packaged cartoned, Powders ordinary combustibles---free flowing-In paper bags(e.g., flours, sugar), Empty Plastic cottage cheese containers Group A Plastics, Cartons unassembled neatly piled.

There is no associated building permit. However, a portion of the building was sprinklered under permit FIR09-00734. An upgrade agreement was filed on 02-10-10 and attached to permit FIR09-00734 for the remainder of the building to be sprinklered.

The pedestrian walkway between the two buildings was approved by the building code examiner.

The fire marshal, Mr. Mark Senteno approved the existing building access and doors. No changes are required, other than a complete fire sprinkler system.

________________________________________

Plan Mod Scope of Work:

Complete the scope work previously approved in the permit FIR09-00734. The work consists of a small tenant finish of a few offices and storage rooms. The new piping layout and pipe sizes match the previously approved layout and pipe sizes; therefore, new hydraulics are not required. This scope of work is all that was reviewed under this plan mod.

Plan Mod Two Scope of Work:
Added one new sprinkler line to provide protection around a flexible duct that was causing an obstruction issue. This scope of work is all that was reviewed under this plan mod.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/14/2011 DONE
Sent to records for scanning.
INSP-Final Inspection11/4/201011/4/201011/4/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/15/201010/15/201010/15/2010PFAIL
DetailsTroy Cobbley
Will be able to final when the insulation is repaired throughout the warehouse.
Inspection Record Card- Fire9/20/2010 9/20/2010 DONE
DetailsBarbara Stitt
Permit Ready to Issue  9/20/2010 DONE
DetailsBarbara Stitt
Telephone call  9/20/2010 DONE
DetailsBarbara Stitt
Called JIm Darr and told him that permit is ready on 9-20-10 @ 8:55am
Issue and Print Permit  9/20/2010 DONE
Plan assigned to (Tim)9/16/2010 9/17/2010 DONE
DetailsTim Frost
9/17/2010 14:07:21 TRF - activity updated through activity FIRA22 from case FIR10-00238.
Sprinkler Plan Check9/17/2010 9/17/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  9/17/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  9/17/2010 DONE
DetailsTim Frost
Plan resubmittals received  9/16/2010  
DetailsTim Frost
plan mod -rec'd 3 sets
INSP-Final Inspection9/3/20109/7/20109/7/2010AFAIL
DetailsTroy Cobbley
The previous wall/draft stop/ needs to be removed out in the warehouse area and Storage Room 115 sprinkler pendants are too far down from the deck but still installed 8" above the t-bar/ceiling. Also in this room the flex ducting is creating alot of obstructions to the sprinkler coverage.
Plan assigned to (Tim)8/20/2010 8/23/2010 DONE
DetailsTim Frost
8/23/2010 08:24:21 TRF - activity updated through activity FIRA22 from case FIR10-00238.
Sprinkler Plan Check8/23/2010 8/23/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  8/23/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/23/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire8/23/2010 8/23/2010 DONE
DetailsPatricia Smith
Telephone call  8/23/2010 DONE
t/c w jim darr at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  8/23/2010 DONE
Details
(F) Reprint permit  8/23/2010 DONE
CHANGE STATUS TO (ISS)  8/23/2010  
Plan resubmittals received  8/20/2010 DONE
DetailsTisha Gallop
Plan Modification: Received three copies of application, submittal binder and plans; taken to Fire Review
INSP-Sprinkler Rough-in/Hydro8/4/20108/4/20108/4/2010PPASS
DetailsTroy Cobbley
The overhead hydro tests of both systems passed.
INSP-Sprinkler Rough-in8/2/20108/2/20108/2/2010PPART
DetailsTroy Cobbley
Need to remove the smoke curtain/draft stop. Need hydro test. Need the "load splitters" hanger assemblies for the main addressed per tim frost. On closet on the second floor has a ceiling and has not been provided sprinkler protection. Also the sprinkler piping located above the first floor ceiling in the office area needs inspection.
INSP-Sprinkler Rough-in/Hydro7/29/20107/30/20107/30/2010ACANC
DetailsTroy Cobbley
justin Phone #: ###-####//cancelled per Justin 7/30 @ 7:18am
INSP-Sprinkler Rough-in7/29/20107/29/20107/29/2010PCANC
DetailsTroy Cobbley
Cancelled due to time constraints caused by Micron plan review. Will be rescheduled for tomorrow per the fitter.
Inspection Record Card- Fire5/26/2010 5/26/2010 DONE
DetailsPatricia Smith
Telephone call  5/26/2010 DONE
t/c w jim darr at ###-#### - permit ready and fees given
Permit Ready to Issue  5/26/2010 DONE
Details
Issue and Print Permit  5/26/2010 DONE
Plan assigned to (Tim)5/24/2010 5/25/2010 DONE
DetailsTim Frost
5/25/2010 16:07:00 TRF - activity updated through activity FIRA22 from case FIR10-00238.
Telephone call  5/25/2010 DONE
Per a phone call with the Fire Marshal. Mr. Mark Senteno he approved the building access as is. Mr. Senteno also approved the existing doors as is. Therefore no new doors are required.
Miscellaneous action  5/25/2010 DONE
Email from Jeff Packham @ Treasure Valley Fire Protection

They will be storing on the racks the following:

Coca products packaged, cartoned.
Powders ordinary combustibles---free flowing-In paper bags (e.g., flours, sugar).
Empty Plastic cottage cheese containers Group A Plastics.
Cartons unassembled neatly piled.

All of the items are stored in the same manner, up to multi row racks, no more than 25' high, with open shelves. The higher hazard sprinkler protection of the group A plastics was determined to protect all of the lesser hazard commodities.
Sprinkler Plan Check5/25/2010 5/25/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  5/25/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  5/25/2010 DONE
DetailsTim Frost
Application received  5/24/2010  
Pending Assignment by SAM5/24/2010 5/24/2010 DONE
DetailsAlexandra L. DeYoung
5/24/2010 16:01:34 ALR - activity updated through activity FIRA158 from case FIR10-00238.