Miscellaneous action | | | 12/2/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/14/2010 | 10/15/2010 | 10/15/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 10/13/2010 | 10/13/2010 | 10/14/2010 | P | PART |
Troy Cobbley
|
|
|
The smoke detectors tested ok. The graphic annunciator lit up the wrong LED when testing the fourth detector. This was fixed with a down load. The fifth detector tested lit up LED's at two locations. Mark fixed this by unplugging the wires to the wrong location. This permit will be finaled with the understanding that the graphic annunciator is to be repaired/corrected for any additional devices. I let Sean Stone and Mark Scharfen know this. This permit can be finaled when the paper work is signed.
|
FIR-Aging Inspection | 9/15/2010 | 9/15/2010 | 9/21/2010 | | NR |
Troy Cobbley
|
|
|
Work is in progress per Mark with Simplex
|
Issue and Print Permit | | | 5/27/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 5/25/2010 | | 5/26/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
5/26/2010 11:47:53 SLC - activity updated through activity FIRA24 from case FIR10-00242.
|
1st review completed | | | 5/26/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 5/26/2010 | | 5/26/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
quick permit approved - no written review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 5/26/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 5/26/2010 | | 5/26/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/26/2010 | | DONE |
|
|
|
left vm for charlie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/26/2010 | | DONE |
|
|
|
|
Application received | | | 5/25/2010 | | |
|
|
|
|