Miscellaneous action | | | 7/28/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 7/1/2010 | 7/2/2010 | 7/2/2010 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 6/30/2010 | 7/1/2010 | 7/1/2010 | A | FAIL |
Troy Cobbley
|
|
|
The Netcon was a 5. Trouble and alarm signals went out. But the activation of a supervisory signal sent a general alarm from the AES panel but a supervisory from the intella-tap. Both signals need to be a supervisory signal.
|
Issue and Print Permit | | | 6/28/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/11/2010 | | 6/24/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
6/24/2010 09:02:01 SLC - activity updated through activity FIRA24 from case FIR10-00279.
|
1st review completed | | | 6/24/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 6/24/2010 | | 6/24/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
approved
|
PLANS TAKEN FRONT DESK ALARM | | | 6/24/2010 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 6/24/2010 | | 6/24/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 6/24/2010 | | DONE |
|
|
|
t/c w lori at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/24/2010 | | DONE |
|
|
|
|
Application received | | | 6/11/2010 | | |
|
|
|
|