Miscellaneous action | | | 9/8/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 8/6/2010 | 8/6/2010 | 8/6/2010 | P | PASS |
Forrest France
|
|
|
Remainder of the scope of work and C/N items finished while on site and verified for completion. Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 8/5/2010 | 8/6/2010 | 8/6/2010 | A | PART |
Forrest France
|
|
|
Reinspection for previous correction items completed acceptable. However, noted fire sprinkler work at the third floor per plan had not been done, also missing an escutcheon at the first floor lobby.
|
INSP-Final Inspection | 8/3/2010 | 8/4/2010 | 8/5/2010 | A | FAIL |
Forrest France
|
|
|
See activity notes dated 8/5
|
INSP-Final Inspection | 8/3/2010 | 8/4/2010 | 8/5/2010 | P | FAIL |
Forrest France
|
|
|
See approved plans for locations of noted correction items at the second floor including missing escutcheons, overspaced heads at one office, missing QR head, lacking coverage at one closet. The existing system appears to be overdue a current annual inspection.
|
INSP-Sprinkler Rough-in/Hydro | 7/29/2010 | 7/29/2010 | 7/29/2010 | A | PART |
Forrest France
|
|
|
1st floor lobby okayed for cover.
|
INSP-Sprinkler Rough-in | 7/28/2010 | 7/28/2010 | 7/28/2010 | P | PART |
Forrest France
|
|
|
Overhead work at the first floor lobby grid ceiling east side (3 pendents) is approved for cover.
|
INSP-Sprinkler Rough-in | 7/15/2010 | 7/16/2010 | 7/16/2010 | A | PASS |
Troy Cobbley
|
|
|
2nd Flr Rough In passed. See the city approved plans for acouple of items that need corrected as marked in red. Piping is ok to cover.
|
INSP-Conference | 7/14/2010 | 7/14/2010 | 7/15/2010 | P | DONE |
Forrest France
|
|
|
On site meeting regarding fire sprinkler coverage at the concealed spaces above the drop ceilings.
|
INSP-Sprinkler Rough-in | 7/14/2010 | 7/15/2010 | 7/15/2010 | A | PART |
Forrest France
|
|
|
Overhead rough-in at the main lobby 100 as per red lined area marked and initialed with today's date is approved for cover. Noted one pendent head at the rolled ceiling in close proximity to a junction box which may present an obstruction depending on type of light fixture installed.
|
Issue and Print Permit | | | 7/13/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 7/2/2010 | | 7/9/2010 | | DONE |
Tim Frost
|
|
|
7/9/2010 10:38:45 TRF - activity updated through activity FIRA22 from case FIR10-00295.
|
Sprinkler Plan Check | 7/9/2010 | | 7/9/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/9/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/9/2010 | | 7/9/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/9/2010 | | DONE |
|
|
|
t/c w shaun at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/9/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/2/2010 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal documents and plans; taken to Fire Review
|
Sprinkler Plan Check | 6/23/2010 | | 6/23/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 6/23/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 6/23/2010 | | DONE |
|
|
|
Emailed review to client
|
Telephone call | | | 6/23/2010 | | DONE |
|
|
|
t/c w shaun at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 6/21/2010 | | |
|
|
|
|