Miscellaneous action | | | 9/20/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 8/26/2010 | 8/27/2010 | 8/27/2010 | P | PASS |
Forrest France
|
|
|
Correction items finished, final fire alarm testing passed. Permit finaled.
|
INSP-Final Inspection | 8/9/2010 | 8/10/2010 | 8/10/2010 | A | NR |
Forrest France
|
|
|
Ken is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus
|
INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 | P | FAIL |
Forrest France
|
|
|
Missing tamper switches at the fire sprinkler riser control valves as shown on approved plans and required per IFC 903.4. Notification appliance at the dining area is the incorrect cd setting, notification device at restroom 114 is not properly installed, provide signage at the FACP and riser room doors per review note # 28.
|
Issue and Print Permit | | | 7/8/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/30/2010 | | 7/7/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
7/7/2010 14:02:27 SLC - activity updated through activity FIRA24 from case FIR10-00305.
|
1st review completed | | | 7/7/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 7/7/2010 | | 7/7/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 7/7/2010 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 7/7/2010 | | 7/7/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/7/2010 | | DONE |
|
|
|
t/c w ken at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/7/2010 | | DONE |
|
|
|
|
Telephone call | | | 7/1/2010 | | DONE |
|
|
|
Spoke to Ken Roule to go over discrepencies on the permit application and to let him know the permit check list was missing. He stated he would re-fill out all the documentation and would bring in or fax in the correct documents.
|
Application received | | | 6/30/2010 | | |
|
|
|
|