Permit Information
Permit NumberFIR10-00307
StatusFinaled
Name ALARMCO
Site Address 10361 W EMERALD ST Unit: 100
Project NameEMERALD TECH BLD # 11 T.I.
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add two duct detectors to the existing fire alarm system, provide connections for monitoring functions for an FM-200 system, and re-circuit an existing tamper switch to accommodate a tenant improvement. There is an existing AES panel with an IntelliTap module installed under FIR10-00280.

Associated building permit: BLD10-00780 (PRECO ELECTRONICS) (BUILDING 11) First time build-out of a new tenant space to occupy a 6,111 sq. ft. portion in existing 11,900 sq. ft. existing SHELL (BLD06-01812) building per approved plans. Work to include construction of interior walls, doors, hardware, millwork, two accessible restrooms, drinking fountain, service sink, suspended ceiling, electrical, mechanical, sprinkler and alarm system modifications for the administrative offices of PRECO Electronics. drs.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  8/13/2010 DONE
FA plans taken to records for scanning
INSP-Final Inspection8/4/20108/5/20108/5/2010APASS
DetailsTroy Cobbley
Permit finaled.
INSP-Final Inspection8/4/20108/4/20108/4/2010PFAIL
DetailsTroy Cobbley
The trouble signal from the fm200 panel was received at the facp as a supervisory. After that was changed we found that the signals were not being received correctly at the monitoring station. I stayed as long as possible but corrections could not be completed. Will need to be rescheduled.
INSP-Final Inspection7/30/20107/30/20107/30/2010PFAIL
DetailsTroy Cobbley
Bill was not available to do the inspection. No one was on site either. No inspection was performed.
INSP-Final Inspection7/19/20107/20/20107/20/2010APART
DetailsTroy Cobbley
A temporary occupancy was given until the interconnections with the FM200 system has been tested.
INSP-Sprinkler Rough-in/Hydro7/16/20107/19/20107/19/2010AFAIL
DetailsTroy Cobbley
The duct smoke detectors and tamper switches tested ok but the facp went into trouble. I left and later returned to the project to see if the issue had been resolved and found that the technicians were still trouble shooting.
INSP-Final Inspection7/16/20107/16/20107/16/2010PCANC
DetailsTroy Cobbley
There are still issues with hvac shutdown. No inspection performed. To be rescheduled for monday morning.
INSP-Final Inspection7/15/20107/16/20107/16/2010ACANC
DetailsTroy Cobbley
Please call Bill at ###-#### with inspection time Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt
Inspection Record Card- Fire7/14/2010 7/14/2010 DONE
DetailsPatricia Smith
Telephone call  7/14/2010 DONE
t/c w lori at ###-#### - permit ready and fees given
Permit Ready to Issue  7/14/2010 DONE
Details
Issue and Print Permit  7/14/2010  
Alarm Plan Check7/13/2010 7/13/2010 PASS
DetailsStephanie L. Cobbley
Plans approved - see review comments
PLANS TAKEN FRONT DESK ALARM  7/13/2010 DONE
Approved plans available at front counter
Plan assigned to (Stephanie)7/1/2010 7/13/2010 DONE
DetailsStephanie L. Cobbley
7/13/2010 14:00:25 SLC - activity updated through activity FIRA24 from case FIR10-00307.
Plan assigned to (Stephanie)7/1/2010 7/13/2010 DONE
DetailsStephanie L. Cobbley
7/13/2010 14:00:25 SLC - activity updated through activity FIRA24 from case FIR10-00307.
Plan resubmittals received  7/6/2010  
DetailsStephanie L. Cobbley
rec'd 2 sets
Telephone call  7/2/2010 DONE
Spoke to Lori to let her know that an FM200 system was submitted for sprinkler review for this project and that it would need to either be incorporated (in a resubmittal) into this submittal packet, or submitted under a separate permit showing it tied in to the fire alarm system. She stated she would find out which direction Alarmco wanted to take and would call me back.
Telephone call  7/2/2010 DONE
Lori called to say they would like to incorporate the FM200 system under this permit.
Telephone call  7/2/2010 DONE
I left a message for Lori letting her know I was denying the plans and they would need to resubmit with the FM200 tie-in and all corresponding documentation.
1st review completed  7/2/2010 DONE
Alarm Plan Check7/2/2010 7/2/2010 FAIL
DetailsStephanie L. Cobbley
resubmittal required
Miscellaneous action  7/2/2010 DONE
Denied plans available at front counter for contractor to pick up
Application received  7/1/2010