Permit Information
Permit NumberFIR10-00321
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 650 N ARMSTRONG PL
Project NameWinco Corp Offices
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of changing an existing light hazard area into an ordinary group II area. Extended coverage sprinklers (14'x14') are being utilized. The existing system is a 3"x2"x1ΒΌ" grid with 6" and 4" underground a 3" backflow preventer and 3" riser. The system riser and backflow preventer will be changed to 4".

(WINCO FOODS - Offices) Permit is to remodel an existing 73,030 square foot office building in three separate areas as defined by submitted plans. Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create 16 new offices, a copy room, and a conference room less than 400 square feet], [demo two offices, a bathroom, and a janitors closet], installation of new doors and hardware, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/14/2011 DONE
Sent to records for scanning.
INSP-Final Inspection12/6/201012/7/201012/7/2010PPASS
DetailsTroy Cobbley
Permit finaled.
FIR-Aging Inspection12/3/201012/3/201012/7/2010 PASS
DetailsTroy Cobbley
INSP-Sprinkler Rough-in8/5/20108/6/20108/6/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in8/5/20108/6/20108/6/2010APASS
DetailsTroy Cobbley
Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in8/3/20108/4/20108/4/2010PPASS
DetailsTroy Cobbley
All of the sprinkler piping is complete and can be covered except for the 1 1/4" main has not been installed or the new pendant head in front of the doorway.
Plan assigned to (Tim)7/8/2010 7/19/2010 DONE
DetailsTim Frost
7/19/2010 11:29:37 TRF - activity updated through activity FIRA22 from case FIR10-00321.
Telephone call  7/19/2010 DONE
Talked with John and asked him to send me the rest of the peaking information for the hydraulic calculations.
On hold waiting for the information.
Sprinkler Plan Check7/19/2010 7/19/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  7/19/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire7/19/2010 7/19/2010 DONE
DetailsPatricia Smith
Telephone call  7/19/2010 DONE
t/c w randy at ###-#### - permit ready and fees given
Permit Ready to Issue  7/19/2010 DONE
Details
Issue and Print Permit  7/19/2010 DONE
Telephone call  7/19/2010 DONE
The fire protection scope of work has been changed. The riser and backflow preventer are to remain as is. The backflow is apparently 4" and the riser is 3". The drawings were changed in the second submittal and not ballooned. The plan reviewer therefore did not notice the change.
Plan resubmittals received  7/15/2010 DONE
DetailsTisha Gallop
received three copies of application, submittal documents and plans; taken to fire review
Telephone call  7/14/2010 DONE
DetailsBarbara Stitt
Left message that plans were denied on 7-14-10 @ 8:00am BAS
Sprinkler Plan Check7/13/2010 7/13/2010 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  7/13/2010 DONE
DetailsTim Frost
Miscellaneous action  7/13/2010 DONE
DetailsTim Frost
Emailed review to contractor
Application received  7/8/2010  
Pending Assignment by SAM7/8/2010 7/8/2010 DONE
DetailsAlexandra L. DeYoung
7/8/2010 16:49:54 ALR - activity updated through activity FIRA158 from case FIR10-00321.