Permit Information
Permit NumberFIR10-00338
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 6401 S EISENMAN RD UNIT 100
Project NameCensport Graphics
Customer Number 
ePlanReview 
Description
The Fire Sprinkler Scope of work consists of providing light hazard protection below a new mezzanine to protect a new office area. Protection is being added for a new spray booth based on Extra Hazard Group II. A new branch line is being added at the roof system due to a new wall. A new dry horizontal sidewall sprinkler is being added in a new outside compressor room. One new sprinkler will be dropped from the overhead system into a new restroom. The existing system is a 2"x4"x2"x2" compound grid designed for .20/2089 + 500 Hose. The existing system is supplied by 6" underground piping and a 6" backflow preventer to a 4" riser.

(CENSPORT GRAPHICS - Quarry Business Complex Ste# 100) Permit is to build out a 2,560 square foot graphics painting studio in an existing 20,268 square foot shell and core building (BLD07-00349). Approval contingent upon adhering to the approved plans on file. Work to include: [construction of interior non-bearing walls to create a fully accessible unisex bathroom, a storage room, a production floor, and offices], installation of new load bearing walls to create a new 460 square foot second floor, installation of new guard rails on mezzanine, installation of new electrical, installation of new accessible bathroom fixtures, installation of new hand sink, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/26/2010 DONE
Sent to records for scanning.
INSP-Final Inspection9/16/20109/17/20109/16/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection9/14/20109/14/20109/14/2010PPART
DetailsForrest France
Pending project related fire alarm permit work.
INSP-Final Inspection9/13/20109/13/20109/13/2010PPART
DetailsForrest France
Final pending control valve supervision at the spray booth.
INSP-Final Inspection9/9/20109/10/20109/10/2010AFAIL
DetailsForrest France
SW head at the exterior compressor room appears painted, provide bags at pendent heads in the spray booth per NFPA 13, upright heads within the 7' zone of the unit heaters must be high temperature per fig.8.3.2.5, control valve at supply to booth heads needs to be supervised.
INSP-Sprinkler Rough-in7/26/20107/26/20107/26/2010PPART
DetailsForrest France
Rough-in with the exception of piping at the spray booth not yet installed is satisfactory. SW head to be provided at the overhead door.
Issue and Print Permit  7/26/2010 DONE
Plan assigned to (Tim)7/14/2010 7/23/2010 DONE
DetailsTim Frost
7/23/2010 10:03:45 TRF - activity updated through activity FIRA22 from case FIR10-00338.
Sprinkler Plan Check7/23/2010 7/23/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
PLANS/APPL TAKEN TO FRONT DESK  7/23/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire7/23/2010 7/23/2010 DONE
DetailsPatricia Smith
Telephone call  7/23/2010 DONE
t/c w don at ###-#### - permit ready and fees given
Permit Ready to Issue  7/23/2010 DONE
Details
Plan resubmittals received  7/21/2010 DONE
DetailsTisha Gallop
received three copies of application, submittal documents and plans; routed to Fire Review
Sprinkler Plan Check7/16/2010 7/16/2010 FAIL
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  7/16/2010 DONE
DetailsTim Frost
Telephone call  7/16/2010 DONE
t/c w don at ###-#### - permit denied - needs to be picked up and resubmitted
Miscellaneous action  7/15/2010 DONE
Sent an email to the contractor as follows:
I will need a completed and signed owner's certificate for this project per the City of Boise checklist. In addition, I need to know exactly what is being stored and how it is package. The height of the storage and aisle widths (if applicable.)

The review will be on hold pending the above information.
Application received  7/14/2010