Miscellaneous action | | | 9/8/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 8/24/2010 | 8/24/2010 | 8/24/2010 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 8/17/2010 | 8/17/2010 | 8/17/2010 | P | PART |
Forrest France
|
|
|
Overhead fire sprinkler work per the scope of remodel is approved for cover at the drop ceilings.
|
INSP-Sprinkler Rough-in | 8/13/2010 | 8/16/2010 | 8/16/2010 | A | FAIL |
Forrest France
|
|
|
Noted one upright head yet to be replaced with quick response, upright coverage at either side of a beam appears overspaced.
|
Plan assigned to (Tim) | 7/16/2010 | | 7/23/2010 | | DONE |
Tim Frost
|
|
|
7/23/2010 10:41:30 TRF - activity updated through activity FIRA22 from case FIR10-00341.
|
Sprinkler Plan Check | 7/23/2010 | | 7/23/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/23/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 7/23/2010 | | 7/23/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/23/2010 | | DONE |
|
|
|
t/c w lisa at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/23/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/23/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/21/2010 | | DONE |
Tisha Gallop
|
|
|
received three copies of application, submittal documents and plans; taken to fire review
|
Sprinkler Plan Check | 7/19/2010 | | 7/19/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/19/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Emailed review to contractor
|
Telephone call | | | 7/19/2010 | | DONE |
|
|
|
t/c w sam at ###-#### - permit denied, needs to be picked up and resubmitted
|
Miscellaneous action | | | 7/19/2010 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Application received | | | 7/16/2010 | | |
|
|
|
|