Miscellaneous action | | | 10/13/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 10/3/2011 | 10/7/2011 | 10/7/2011 | A | PASS |
Forrest France
|
|
|
Corrections and adjustments made while on site. Network capabilities tested satisfactory, re-inspection items passed. Scope of fire alarm permit finaled.
|
INSP-Conference | 9/23/2011 | 9/23/2011 | 9/23/2011 | P | DONE |
Forrest France
|
|
|
Regarding acceptance testing per NFPA 72 2007 ch 10.
|
INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 | A | FAIL |
Forrest France
|
|
|
Began testing at the high school brick building address 5493 and modulars #1 and #2. Noted corrections include items on review notes # 7, 20, 25 and 13.
|
Plan assigned to (Stephanie) | 8/15/2011 | | 8/17/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 8/17/2011 | | DONE |
|
|
|
Spoke to David and requested two new sets of drawings that incorporate the original review comments and redlines. I explained that the original review stated a plan modification would be required incorporating the redlines, however the plan modification received only incorporated the field modifications and not the original review comments/redlines. He indicated he would have the changes made and the new sets brought downtown today.
|
Plan resubmittals received | | | 8/17/2011 | | |
Christina Prado
|
|
|
Plan mod received for additional info needed on sheets FA-0.0, FA-1.0, FA-1.1, FA-2.0, FA-2.0 7 FA -2.3. eceived two copies of all sheets and routed to Stephanie for further review
|
Alarm Plan Check | 8/17/2011 | | 8/17/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification plans approved with redlines and review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/17/2011 | | DONE |
|
|
|
Approved redlined plan modifications available at front counter.
|
Inspection Record Card- Fire | 8/17/2011 | | 8/17/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/17/2011 | | DONE |
|
|
|
t/c w joe - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 8/17/2011 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/17/2011 | | DONE |
Barbara Stitt
|
|
|
Issue plan modification
|
(F) Reprint permit | | | 8/17/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 8/15/2011 | | DONE |
|
|
|
Plan Mod received 8/12/11
|
FIR-Aging Inspection | 3/21/2011 | 3/21/2011 | 3/21/2011 | | NR |
Forrest France
|
|
|
No call for inspection
|
FIR-Aging Inspection | 1/6/2011 | 1/6/2011 | 1/6/2011 | | DONE |
Forrest France
|
|
|
In progress
|
INSP-Conference | 10/18/2010 | 10/18/2010 | 10/18/2010 | A | DONE |
Forrest France
|
|
|
On site meeting with Ray Criner, Engine 22, and property representative regarding status of permit work in progress.
|
Issue and Print Permit | | | 7/26/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/20/2010 | | 7/23/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
7/23/2010 15:29:43 SLC - activity updated through activity FIRA24 from case FIR10-00346.
|
1st review completed | | | 7/23/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 7/23/2010 | | 7/23/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved with redlines and review comments. A plan modification will be required to be submitted and approved prior to scheduling a final inspection.
|
PLANS TAKEN FRONT DESK ALARM | | | 7/23/2010 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 7/23/2010 | | 7/23/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/23/2010 | | DONE |
|
|
|
t/c w gill at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/23/2010 | | DONE |
|
|
|
|
Telephone call | | | 7/22/2010 | | DONE |
|
|
|
Spoke to Lee regarding discrepencies in the project addressing and several correction items (see scope of work for clarifications). Due to scheduling, Lee has chosen to have me approve the drawings with the understanding that a plan modification will need to be submitted and approved prior to calling for an inspection. He was informed that there will be additional review fees involved.
|
Telephone call | | | 7/22/2010 | | DONE |
|
|
|
Spoke with Lee regarding the fire alarm permit for both buildings. I advised him that having both building fire alarm permits attached to the single building permit for the Arts & Science building may pose a problem during the permit finaling. I suggested he separate the permit into two fire permits to avoid having the one building held up by the other. He stated he was aware but wanted to keep the single permit because the work will all be done at once.
|
Application received | | | 7/20/2010 | | |
|
|
|
|
INSP-Final Inspection | 9/20/2011 | 9/21/2011 | | P | |
Forrest France
|
|
|
Please cantact Jeremy at ###-####. This inspection is for a school and will need to be scheduled for 3pm or later so classes will not be disrupted. Thank you. Phone #: ###-#### >> Inspection requested via web by David Dilley
|