Miscellaneous action | | | 6/8/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 2/16/2011 | 2/17/2011 | 2/17/2011 | A | PASS |
Forrest France
|
|
|
Noted correction items verified for completion. Fire sprinkler permit final approved.
|
INSP-Final Inspection | 2/15/2011 | 2/16/2011 | 2/16/2011 | A | PASS |
Forrest France
|
|
|
Completed final walkthrough, noted pendent heads at two locations 2nd floor yet to be changed to quick response type, one upright at the laundry needs uncovered, provide current tags at the riser, riser monitoring test pending.
|
INSP-Final Inspection | 2/14/2011 | 2/15/2011 | 2/15/2011 | A | PART |
Forrest France
|
|
|
don Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 2/1/2011 | 2/2/2011 | 2/2/2011 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test passed for both wet systems.
|
INSP-Sprinkler Rough-in | 12/13/2010 | 12/14/2010 | 12/14/2010 | A | PART |
Forrest France
|
|
|
See approved plan set for clouded areas okayed for cover marked with today's date. Also see annotations regarding correction items at some locations.
|
INSP-Sprinkler Rough-in | 12/13/2010 | 12/13/2010 | 12/13/2010 | A | PART |
Forrest France
|
|
|
Don Phone #: ###-####
|
INSP-Sprinkler Rough-in | 12/9/2010 | 12/9/2010 | 12/9/2010 | P | DEFR |
Forrest France
|
|
|
don Phone #: ###-####
|
FIR-Aging Inspection | 11/12/2010 | 11/12/2010 | 11/12/2010 | | DONE |
Forrest France
|
|
|
Site work in progress, construction underway.
|
INSP-Sprinkler Rough-in | 9/7/2010 | 9/8/2010 | 9/8/2010 | A | PART |
Forrest France
|
|
|
See sheet FP1 on stamped plan set for red-lined areas inspected and okayed for cover marked with today's date. Discussed project related demo permit.
|
Plan assigned to (Tim) | 7/21/2010 | | 8/2/2010 | | DONE |
Tim Frost
|
|
|
8/2/2010 10:15:26 TRF - activity updated through activity FIRA22 from case FIR10-00357.
|
Sprinkler Plan Check | 8/2/2010 | | 8/2/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/2/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/2/2010 | | 8/2/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/2/2010 | | DONE |
|
|
|
t/c w brodie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/2/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/2/2010 | | |
|
|
|
|
Plan resubmittals received | | | 7/30/2010 | | DONE |
Tisha Gallop
|
|
|
recevied four copies of application, submittal documents and plans. Taken to Fire Review.
|
Sprinkler Plan Check | 7/27/2010 | | 7/27/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 7/27/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 7/27/2010 | | DONE |
|
|
|
Emailed comments to contractor
|
Telephone call | | | 7/27/2010 | | DONE |
|
|
|
t/c w brodie at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/21/2010 | | |
|
|
|
|