Miscellaneous action | | | 9/20/2010 | | DONE |
|
|
|
FA plans taken to records for scanning.
|
INSP-Final Inspection | 7/30/2010 | 7/30/2010 | 7/30/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 7/29/2010 | 7/30/2010 | 7/30/2010 | A | PASS |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Gobler
|
Issue and Print Permit | | | 7/28/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/26/2010 | | 7/27/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
7/27/2010 09:05:58 SLC - activity updated through activity FIRA24 from case FIR10-00364.
|
Plan assigned to (Stephanie) | 7/26/2010 | | 7/27/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
7/27/2010 09:05:58 SLC - activity updated through activity FIRA24 from case FIR10-00364.
|
1st review completed | | | 7/27/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 7/27/2010 | | 7/27/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written comments
|
PLANS TAKEN FRONT DESK ALARM | | | 7/27/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 7/27/2010 | | 7/27/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 7/27/2010 | | DONE |
|
|
|
left vm for robert at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/27/2010 | | DONE |
|
|
|
|
Application received | | | 7/26/2010 | | |
|
|
|
|