Miscellaneous action | | | 10/26/2010 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 9/20/2010 | 9/20/2010 | 9/20/2010 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in | 9/8/2010 | 9/8/2010 | 9/8/2010 | P | PART |
Forrest France
|
|
|
Overhead rough-in okayed for cover at the grid ceilings, one overspaced head relocated while on site.
|
INSP-Sprinkler Rough-in/Hydro | 8/20/2010 | 8/20/2010 | 8/20/2010 | P | PART |
Forrest France
|
|
|
|
INSP-Sprinkler Rough-in | 8/9/2010 | 8/9/2010 | 8/10/2010 | P | PART |
Forrest France
|
|
|
Okay to cover overhead work at two restrooms as marked on stamped plan set with today's date.
|
Issue and Print Permit | | | 8/4/2010 | | DONE |
|
|
|
|
Plan assigned to (Tim) | 7/30/2010 | | 8/3/2010 | | DONE |
Tim Frost
|
|
|
8/3/2010 13:51:28 TRF - activity updated through activity FIRA22 from case FIR10-00374.
|
Plan resubmittals received | | | 8/3/2010 | | |
|
|
|
received 3 sets of plans / applications sent to Tim Frost.
|
Sprinkler Plan Check | 8/3/2010 | | 8/3/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/3/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 8/3/2010 | | 8/3/2010 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 8/3/2010 | | DONE |
|
|
|
|
Telephone call | | | 8/3/2010 | | DONE |
|
|
|
Called Jim Darr and told him that permit is ready & fees due on 8-3-10 @ 2:10pm BAS
|
Sprinkler Plan Check | 8/2/2010 | | 8/2/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS TAKEN FRONT DESK ALARM | | | 8/2/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 8/2/2010 | | DONE |
|
|
|
Emailed review to contractor
|
Telephone call | | | 8/2/2010 | | DONE |
|
|
|
t/c w jim darr at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 7/30/2010 | | |
|
|
|
|