Miscellaneous action | | | 12/2/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/10/2010 | 11/10/2010 | 11/10/2010 | P | PASS |
Troy Cobbley
|
|
|
The damper was repaired and checked for function. Permit finaled
|
FIR-Aging Inspection | 11/10/2010 | 11/10/2010 | 11/10/2010 | P | CANC |
Troy Cobbley
|
|
|
Wrong inspection type.
|
INSP-Final Inspection | 11/10/2010 | 11/10/2010 | 11/10/2010 | P | FAIL |
Troy Cobbley
|
|
|
The damper failed to close when the smoke detector was activated.
|
CHANGE STATUS TO (ISS) | | | 11/9/2010 | | DONE |
Tisha Gallop
|
|
|
picked up modification
|
Plan resubmittals received | | | 11/1/2010 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: Received over the fax, one copy of application and drawings; taken to SLC.
|
Plan assigned to (Stephanie) | 11/1/2010 | | 11/1/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 11/1/2010 | | 11/1/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit plan modification approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/1/2010 | | DONE |
|
|
|
Approved plan modification documents available at front counter
|
Inspection Record Card- Fire | 11/1/2010 | | 11/1/2010 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 11/1/2010 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 11/1/2010 | | DONE |
Barbara Stitt
|
|
|
Left message for Ken Webster that permit is ready & fees due on 11-1-10 @ 4:00 pm
|
Telephone call | | | 9/20/2010 | | DONE |
|
|
|
Spoke to Mike at Allied General. He stated that the permit application was wrong to state the scope was for HVAC shut down. They actually wanted to use a Duct Detector for fire/smoke damper shut down. I let him know that the duct detectors are not listed for f/s damper shut down and that he would need to submit a plan modification putting the in-duct detector back in.
|
INSP-Final Inspection | 9/10/2010 | 9/13/2010 | 9/13/2010 | A | FAIL |
Troy Cobbley
|
|
|
The duct smoke detector is being used for fire/smoke damper operation which is outside of the duct smoke detectors listing since it is not listed to 0cfm. I spoke to Randy on site and Mike in the office. No testing was performed.
|
INSP-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 | A | CANC |
Forrest France
|
|
|
Overbooked
|
Issue and Print Permit | | | 8/16/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/11/2010 | | 8/13/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
8/13/2010 11:10:55 SLC - activity updated through activity FIRA24 from case FIR10-00395.
|
1st review completed | | | 8/13/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 8/13/2010 | | 8/13/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 8/13/2010 | | DONE |
|
|
|
Approved quick permit plans available at front counter
|
Inspection Record Card- Fire | 8/13/2010 | | 8/13/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 8/13/2010 | | DONE |
|
|
|
t/c w ken at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/13/2010 | | DONE |
|
|
|
|
Application received | | | 8/11/2010 | | |
|
|
|
|