Permit Information
Permit NumberFIR10-00398
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 3176 S DENVER WAY
Project NameST LUKE'S REFERENCE LABORATORY
Customer Number 
ePlanReviewNo
Description
1/14/11: PLAN MODIFICATION (10 initiating devices affected): This plan modification is to show field modifications to some notification device placement, provide in-duct detectors to f/s dampers not originally known to be a part of the project, and to eliminate some of the duct detectors not needed due to common returns.
8/20/10:
This fire alarm permit is to provide notification and initiating devices to accommodate a tenant improvement. Devices include all new horn/strobes (any existing notification devices are to be removed), pull stations, HVAC monitoring, and in-duct detectors for new F/S dampers. The notification devices are to be connected to new remote power supplies. The initiating devices are to be connected to the existing fire alarm signal line circuit. This building does not require the full manual system (only sprinkler monitoring, elevator recall, and HVAC), however it was requested by the customer.
NOTE TO INSPECTOR: The fire sprinkler permit (FIR10-00125) is attached to the demo building permit (BLD09-02080).
Associated building permit: BLD10-00044 (ST. LUKE'S - REFERENCE LABORATORY) To remodel an existing two story 31,625 sq. ft. building into a medical laboratory per approved plans. Demolition work is under separate permit, BLD09-02080. Work to include construction of interior walls in conjunction with remaining existing walls to create office, work, laboratory and support areas; conference / training room on second floor with existing offices; upgrade restrooms, showers, drinking fountains, doors, door hardware and clear floor spaces & latch side clearance at all doors; work on electrical, mechanical, plumbing, sprinkler, alarm and security systems to comply with current adopted codes and ordinances. Separate applications and permits required for sprinkler & alarm system modifications as regulated by the fire department, before being worked on. NOTE: This building is fully fire sprinklered with all heads being changed to quick response to allow non-rated corridors. Drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection1/21/20111/21/20111/21/2011PPASS
DetailsForrest France
Inspection notes 1/21/11- Flow switch repaired and retested okay. Audible notification adjustments okayed. Fire alarm permit final approved.
INSP-Final Inspection1/20/20111/20/20111/21/2011PPART
DetailsForrest France
Inspection notes 1/20/11- Completed acceptance testing including initiating and notification devices, sprinkler monitoring, and elevator control functions. Verified offsite monitoring. Flashing hat at the elevator is not required due to original installation date of the equipment per plan review. Flow switch at the wet system riser did not pass operational testing. Remainder of items tested okay.
INSP-Final Inspection1/18/20111/19/20111/21/2011APART
DetailsForrest France
Inspection notes 1/19/11- Completed project walkthrough- noted some locations where audibility may be insufficient, cd rating at the second floor breakroom adjusted, one DD is supply side located, "shadowed" areas to be verified during functional testing. Verified as-builts per request.
Alarm Plan Check1/14/2011 1/14/2011 PASS
DetailsStephanie L. Cobbley
Plan modification approved with redlines and review comments. As-builts shall be required at time of inspection.
PLANS TAKEN FRONT DESK ALARM  1/14/2011 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire1/14/2011 1/14/2011 DONE
DetailsPatricia Smith
Telephone call  1/14/2011 DONE
t/c w larry - permit (plan mod) ready and fees given
Permit Ready to Issue  1/14/2011 DONE
Details
CHANGE STATUS TO (ISS)  1/14/2011 DONE
DetailsChristina Prado
Plans picked up 1-14-11
Plan resubmittals received  1/3/2011 DONE
DetailsStephanie L. Cobbley
Received two copies of application, Information packets and plans E141-E143, FACP, NAC, NDL and site plan
INSP-Conference12/21/201012/22/201012/22/2010ADONE
DetailsForrest France
Regarding field modifications and plan resubmital.
FIR-Aging Inspection11/12/201011/12/201011/12/2010 DONE
DetailsForrest France
Site work in progress, construction underway.
INSP-Conference8/31/20108/31/20109/1/2010PDONE
DetailsForrest France
Regarding notification appliance locations with respect to equipment layout at one area.
Issue and Print Permit  8/24/2010 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)8/12/2010 8/20/2010 DONE
DetailsStephanie L. Cobbley
8/20/2010 09:19:51 SLC - activity updated through activity FIRA24 from case FIR10-00398.
Telephone call  8/20/2010 DONE
John with CH2MHILL called to answer the questions I had and clarify discrepencies in the plans. I asked him to email with what we'd discussed over the phone. I recieved that email a short time later.
1st review completed  8/20/2010 DONE
Alarm Plan Check8/20/2010 8/20/2010 PASS
DetailsStephanie L. Cobbley
Approved with redlines
PLANS TAKEN FRONT DESK ALARM  8/20/2010 DONE
Approved redlined plans available at front counter
Inspection Record Card- Fire8/20/2010 8/20/2010 DONE
DetailsPatricia Smith
Telephone call  8/20/2010 DONE
left vm for larry at ###-#### - permit ready and fees given
Permit Ready to Issue  8/20/2010 DONE
Details
Telephone call  8/19/2010 DONE
Spoke to Rick at NWS to go over some areas of the plans that I needed clarification on. He was able to answer some of my questions, and for the other clarifications he let me know I would need to call the engineer.
Telephone call  8/19/2010 DONE
Left a message of John Hatten at CH2MHILL letting him know I have questions on the fire alarm plans.
Application received  8/12/2010