Permit Information
Permit NumberFIR10-00409
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 10221 W EMERALD ST
Project NamePiramal Critical Care
Customer NumberSEE COMMENTS
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding, relocating and removing sprinklers to accommodate a new tenant. Approximately, 27 sprinklers are being changed from pendent to upright sprinklers. A new partial branch line will be connected to the existing 3" main and then connected to the existing 1ΒΌ" branch lines in this grid type piping system. The design is based on boxed or pallet storage not to exceed 5' in height per Bob Hosac of RS Hosac

Building Department Scope:

Permit for a tenant improvement to an existing 19,035 sq. ft. building to combine all existing tenant spaces into one tenant space with work to include the removal of interior non-bearing partition walls, removal of one restroom and the extension of some of the interior partition walls up to the roof deck. The existing lighting fixtures will be reused. All work to be done per the approved plans, plan review report and any notations. This is a fully sprinklered building; any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by the Boise City Fire Department. No Racking is allowed under this permit. A separate racking permit is required for any racking over 8 feet in height. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/26/2010 DONE
Sent to records for scanning.
INSP-Final Inspection9/1/20109/1/20109/1/2010PPASS
DetailsTroy Cobbley
Permit finaled
Override - Parcel Holds9/1/20101/1/19009/1/2010  
this inspection is for fire permit
INSP-Final Inspection8/30/20108/31/20108/31/2010PFAIL
DetailsTroy Cobbley
Two heads as discussed need to have separate supplies from the branchline since the area does not appear to qualify for "Room Design" method of hydraulic calculations. I also noted that one pendant head in the office area is located too close to a wall and will need to be relocated as well as missing canopies provided. The fire sprinkler system has not been inspected for 10 years.
Override - Parcel Holds8/30/20101/1/19008/30/2010  
WILL CHECK WITH
Plan assigned to (Tim)8/19/2010 8/26/2010 DONE
DetailsTim Frost
8/26/2010 13:31:46 TRF - activity updated through activity FIRA22 from case FIR10-00409.
Sprinkler Plan Check8/26/2010 8/26/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  8/26/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  8/26/2010 DONE
DetailsTim Frost
Override - Parcel Holds  8/26/2010  
Inspection Record Card- Fire8/26/2010 8/26/2010 DONE
DetailsPatricia Smith
Telephone call  8/26/2010 DONE
t/c w shaun at ###-#### - permit ready and fees given
Override - Parcel Holds  8/26/2010  
Permit Ready to Issue  8/26/2010 DONE
Details
Override - Parcel Holds  8/26/2010  
Issue and Print Permit  8/26/2010  
Miscellaneous action  8/20/2010 DONE
Called DeBest and told them that I need an owner's certificate and list of what they are storing and how it is being stored.
Application received  8/19/2010