Permit Information
Permit NumberFIR10-00423
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1221 W IDAHO ST
Project NameIdaho Power Company
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to extend the existing voice evacuation system and add smoke detectors to accommodate a tenant remodel. A new NAC remote power supply/panel is being provided to accommodate the visual portion of the new notification devices. The speakers will be added to existing speaker circuits.

Associated building permit: BLD10-01305 (IDAHO POWER COMPANY) Permit for minor interior improvements to the to the second, third, fifth and sixth floors. The work on the third, fifth and sixth is work that has already been completed and is minor in nature consisting of the construction of Steelcase Pathways demountable wall system to create small office and conference room areas with no change in occupant load. The wall system is to be installed per ESR 1829 attached to the plans. Work on the second floor is similar in nature with K-Wall systems approved under previous permits with work to include retrofit of lighting with more efficient products minor HVAC work and related interior finishes with no change in occupant load. The existing corridor is to remain in tact. All work to be done per the approved plans. This is a fully sprinklered building any alterations to the sprinkler system will require a separate permit and shall comply with NFPA13 as regulated by the fire department. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  12/2/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/24/20109/24/20109/24/2010PPASS
DetailsForrest France
Fire alarm permit work okayed for final, address switch repaired while on site. Inspection passed.
INSP-Alarm Testing9/24/20109/24/20109/24/2010PPASS
DetailsForrest France
Reinspection for noted correction items passed at the 2nd, 5th and 6th floors.
INSP-Final Inspection9/23/20109/23/20109/24/2010PFAIL
DetailsForrest France
Correction items include relocate three SD too close to HVAC diffusers, adjust cd setting per plan at one room 5th floor, voice evacuation message does not meet intelligibility or audibility requirements.
INSP-Alarm Testing9/22/20109/22/20109/22/2010APART
DetailsForrest France
After hours inspection scheduled 9/23 PM.
Issue and Print Permit  9/14/2010 DONE
Plan assigned to (Stephanie)8/30/2010 9/13/2010 DONE
DetailsStephanie L. Cobbley
9/13/2010 15:33:44 SLC - activity updated through activity FIRA24 from case FIR10-00423.
Plan assigned to (Stephanie)8/30/2010 9/13/2010 DONE
DetailsStephanie L. Cobbley
9/13/2010 15:33:44 SLC - activity updated through activity FIRA24 from case FIR10-00423.
Telephone call  9/13/2010 DONE
Mark with Simplex called for Charlie to find out what information I needed. I let him know I needed information on the existing amplifiers (i.e. what total watts per amp are being used, which speaker circuits go to which amps, how many amplifiers are available etc...) as well as the data sheet for the 4100+. He let me know he'd email the information as soon as possible.
Miscellaneous action  9/13/2010 DONE
Recieved an email with the data sheet as requested, a generic one-line, and text indicating each amplifier is capable of 100 watts.
1st review completed  9/13/2010 DONE
Alarm Plan Check9/13/2010 9/13/2010 PASS
DetailsStephanie L. Cobbley
plans approved - see review comments
PLANS TAKEN FRONT DESK ALARM  9/13/2010 DONE
Approved plans available at front counter
Inspection Record Card- Fire9/13/2010 9/13/2010 DONE
DetailsPatricia Smith
Telephone call  9/13/2010 DONE
left vm for charlie at ###-#### - permit ready and fees given
Permit Ready to Issue  9/13/2010 DONE
Details
Telephone call  9/10/2010 DONE
Spoke with Charlie at Simplex to request information on the 4100+ the speakers are being added to. I explained I need to know the available watts and which amp each of the speaker circuits are tied in to. He let me know he would not have the information available until Monday (9/13/10)
Application received  8/30/2010