Permit NumberFIR10-00424
StatusFinaled
Name TAYLOR BROTHERS FIRE & SAFETY INC
Site Address 2613 S VISTA AVE
Project NameHOLIDAY INN EXPRESS
Customer Number 
ePlanReviewNo
Description
3/2/11 PLAN MODIFICATION (no initiating devices affected): This plan modification is to revise the one-line to indicate the new devices are on the new NAC panel rather than on with existing devices and to include the internal card needed to monitor the panel for integrity to report the appropriate alarm, trouble, and supervisory signals.

10/8/2010:This fire alarm permit is to provide a new NAC panel and new notification devices to upgrade existing rooms to meet ADA requirements. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/15/2011 DONE
Drawings taken to records for scanning.
INSP-Final Inspection3/3/20113/3/20113/3/2011PPASS
DetailsForrest France
Scope of permit work passed functional testing at three ADA unit restrooms. Plan resubmital verified, permit finaled.
CHANGE STATUS TO (ISS)  3/3/2011 DONE
DetailsBarbara Stitt
(F) Reprint permit  3/3/2011 DONE
DetailsBarbara Stitt
Alarm Plan Check3/2/2011 3/2/2011 PASS
DetailsStephanie L. Cobbley
Plan modification approved
PLANS TAKEN FRONT DESK ALARM  3/2/2011 DONE
Approved plan modification documents available at front counter
Permit Ready to Issue  3/2/2011 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire3/2/2011 3/2/2011 DONE
DetailsBarbara Stitt
Telephone call  3/2/2011 DONE
DetailsBarbara Stitt
Left message for Robert King that permit is ready & fees due on 3-2-11 @ 4:10pm///BAS
Plan assigned to (Stephanie)2/24/2011 3/2/2011 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  2/24/2011  
DetailsBarbara Stitt
FIR-Aging Inspection2/15/20112/15/20112/15/2011 FAIL
DetailsForrest France
Ref. correction notice items.
INSP-Final Inspection12/13/201012/13/201012/13/2010PFAIL
DetailsTroy Cobbley
The NAC circuit did not report a trouble to the FACP. The FACP did not report a trouble to the monitoring station and did not activate a trouble signal at the remote annunciator. This is a requirement of NFPA 72 4.4.7.1. The sprinkler tamper switches reported a toruble signal at the remote annunciator and at the monitoring station. The lenses of the new strobes are not mounted between 80" and 96". Also as-builts are needed which show all of the existing a/v's remaining on the existing panel and only the three new a/v's being added to the new NAC panel. Revised EOL voltage drop calculations are needed and battery calculations are needed. There was no actual testing of devices.
INSP-Final Inspection12/6/201012/7/201012/8/2010PNH
DetailsForrest France
Issue and Print Permit  10/13/2010 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)8/30/2010 10/8/2010 DONE
DetailsStephanie L. Cobbley
Miscellaneous action  10/8/2010 DONE
Quick permit changed to regular permit due to extent of work being done.
Alarm Plan Check10/8/2010 10/8/2010 PASS
DetailsStephanie L. Cobbley
Plans approved with comments
PLANS TAKEN FRONT DESK ALARM  10/8/2010 DONE
Approved plans available at front counter
Inspection Record Card- Fire10/8/2010 10/8/2010 DONE
DetailsPatricia Smith
Telephone call  10/8/2010 DONE
t/c w shelly at ###-####- permit ready and fees given
Permit Ready to Issue  10/8/2010 DONE
Details
Plan resubmittals received  10/4/2010  
DetailsBarbara Stitt
1st review completed  9/2/2010 DONE
Alarm Plan Check9/2/2010 9/2/2010 FAIL
DetailsStephanie L. Cobbley
Quick permit denied. Plans do not meet code requirements for hotel rooms w/ADA requirements.
Telephone call  9/2/2010 DONE
Spoke with Robert to let him know why the plans were being denied.
Miscellaneous action  9/2/2010 DONE
Faxed Robert with Taylor Brothers the first sheet of his submitted application with comments explaining some of why the plans were being denied.
Application received  8/30/2010