Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberFIR10-00432
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 409 S COLE RD
Project NameHARRISON PLAZA SUITE HOTEL
Customer Number 
ePlanReviewNo
Description
This quick permit is to add devices for elevator recall and shunt trip functions. The lobby smoke detectors are to activate recall functions even when the rest of the circuit is in alarm. No general alarm functions shall operate elevator recall functions. No written review comments. No associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection12/22/201012/22/201012/23/2010PPASS
DetailsTroy Cobbley
Permit finaled
Miscellaneous action  12/20/2010 DONE
Received requested as-built information
INSP-Final Inspection12/16/201012/17/201012/17/2010AFAIL
DetailsTroy Cobbley
Re-label zone #1 since it now includes the basement zone. This arrangement has been approved by the plan reviewer. Also provide as-builts as discussed.
FIR-Aging Inspection12/16/201012/16/201012/16/2010 NR
DetailsTroy Cobbley
Has been called in for tomorrow morning.
Issue and Print Permit  9/16/2010 DONE
Case Summary  9/15/2010 DONE
Plan assigned to (Stephanie)9/2/2010 9/10/2010 DONE
DetailsStephanie L. Cobbley
9/10/2010 13:46:14 SLC - activity updated through activity FIRA24 from case FIR10-00432.
Plan assigned to (Stephanie)9/2/2010 9/10/2010 DONE
DetailsStephanie L. Cobbley
9/10/2010 13:46:14 SLC - activity updated through activity FIRA24 from case FIR10-00432.
Plan resubmittals received  9/10/2010 DONE
Alarm Plan Check9/10/2010 9/10/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  9/10/2010 DONE
Approved quick permit documents available at front counter
Inspection Record Card- Fire9/10/2010 9/10/2010 DONE
DetailsPatricia Smith
Telephone call  9/10/2010 DONE
left vm for john at ###-#### - permit ready and fees given
Permit Ready to Issue  9/10/2010 DONE
Details
1st review completed  9/3/2010 DONE
Telephone call  9/3/2010 DONE
Spoke to Earl at Fire Sentry Systems to go over issues with the elevator recall functions on the zoned panel and missing information on the matrix. Based on the conversation, a resubmittal is required because smoke detector relay base and functions were not provided, the 120v monitoring for the shunt trip was not indicated, and incorrect functions for the elevator fireman's hat light were not shown on the matrix.
Alarm Plan Check9/3/2010 9/3/2010 FAIL
DetailsStephanie L. Cobbley
Plans failed. Need more detailed information for the devices used for elevator recall and shunt trip.
Application received  9/2/2010