Miscellaneous action | | | 6/8/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 4/13/2011 | 4/13/2011 | 4/13/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 4/4/2011 | 4/5/2011 | 4/5/2011 | A | FAIL |
Troy Cobbley
|
|
|
One of the new earthquake bracing attachment points needs to be taken to the deck as discussed. Also the sidewall sprinkler heads are listed to be installed 6" to 12" below the deck. Some of them are actually installed 4" below the deck.
|
INSP-Final Inspection | 4/4/2011 | 4/4/2011 | 4/4/2011 | P | CANC |
Troy Cobbley
|
|
|
Canceled due to time constraints. Rescheduled for tomorrow morning.
|
INSP-Final Inspection | 3/22/2011 | 3/23/2011 | 3/23/2011 | P | FAIL |
Troy Cobbley
|
|
|
Provide the missing earthquake bracing at the east end of the system and change the lateral bracing to a longitudinal brace at the 2 1/2" connection point per the plans. Also many of the new sidewall heads exceed 6" down from the deck. Per the detail on the plans the heads are to be installed at 6". There was no data sheet provided to verify if the heads could be up to 10" below the deck as some are installed now.
|
FIR-Aging Inspection | 1/5/2011 | 1/5/2011 | 1/12/2011 | | NR |
Troy Cobbley
|
|
|
work is in progress per trent
|
INSP-Final Inspection | 1/11/2011 | 1/12/2011 | 1/11/2011 | P | CANC |
Troy Cobbley
|
|
|
Trent Bice is the contact. Please call one hour before inspection to ensure someone will be there to let you in. Phone #: ###-#### >> Inspection requested via web by Trent Bice Inspection cancelled from web by: Trent Bice
|
Issue and Print Permit | | | 9/27/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 9/3/2010 | | 9/23/2010 | | DONE |
Tim Frost
|
|
|
9/23/2010 09:41:46 TRF - activity updated through activity FIRA22 from case FIR10-00443.
|
Sprinkler Plan Check | 9/23/2010 | | 9/23/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 9/23/2010 | | 9/23/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 9/23/2010 | | DONE |
|
|
|
left message for trent at ###-#### - permit ready and fees given - must pay past due fees before this one can be picked up
|
Permit Ready to Issue | | | 9/23/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/22/2010 | | |
Tim Frost
|
|
|
rec'd 3 sets
|
Sprinkler Plan Check | 9/8/2010 | | 9/8/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 9/8/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 9/8/2010 | | DONE |
|
|
|
Emailed review to contractor.
|
Telephone call | | | 9/8/2010 | | DONE |
|
|
|
t/c w trent at ###-#### - permit denied -needs to be picked up and resubmitted
|
Application received | | | 9/3/2010 | | |
|
|
|
|
Pending Assignment by SAM | 9/3/2010 | | 9/3/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
9/3/2010 14:29:04 ALR - activity updated through activity FIRA158 from case FIR10-00443.
|