Permit Information
Permit NumberFIR10-00483
StatusFinaled
Name RCI ELECTRICAL SOLUTIONS
Site Address 877 W FRONT ST
Project NameTHE ASPEN-TURNER R.E.G. TI
Customer Number 
ePlanReviewNo
Description
This quick permit is to relocate a strobe only and add two new speaker/strobes to the existing fire alarm system to accomodate a tenant improvement. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems.The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. A building map shall be posted at the FACP indicating the type and location of all alarm initiating devices, by device address or zone number. Provide updated map reflecting the floor plan and all initiating device locations. 2007 NFPA 72 4.4.6.1. There are no written review comments. Associated building permit: BLD10-01322 (TURNER REAL ESTATE GROUP - 1ST STORY - THE ASPEN BUILDING) This building is fire sprinklered because it is a high rise. To prepare an existing 1,102 square foot shell space located on the 1st story of the Aspen Building for occupancy as a real estate office. Work is to include interior nonbearing walls, suspended acoustical ceilings, ceiling shelf, millwork, and finishes. The restroom was installed under the shell permit and is required to be fully accessible to the disabled. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  12/2/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/13/201010/14/201010/14/2010APASS
DetailsForrest France
Fire alarm work completed satisfactory, functional testing passed. Permit finaled.
INSP-Final Inspection10/12/201010/13/201010/13/2010PCANC
DetailsForrest France
barry Phone #: ###-#### Inspection cancelled from web by: BARRY KENDALL
Issue and Print Permit  10/1/2010  
Plan assigned to (Stephanie)9/30/2010 9/30/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  9/30/2010 DONE
Alarm Plan Check9/30/2010 9/30/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  9/30/2010 DONE
approved documents available at front counter
Case Summary  9/30/2010 DONE
Inspection Record Card- Fire9/30/2010 9/30/2010 DONE
DetailsPatricia Smith
Telephone call  9/30/2010 DONE
left vm for barry at ###-#### - permit ready and fees given
Permit Ready to Issue  9/30/2010 DONE
Details
Application received  9/29/2010  
Pending Assignment by SAM9/29/2010 9/29/2010 DONE
DetailsPatricia Smith
9/29/2010 13:58:25 P_S - activity updated through activity FIRA158 from case FIR10-00483.