Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberFIR10-00484
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 1500 W SHORELINE DR
Project NameST. LUKES/SHORELINE TECH TI
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a new remote power supply and new notification devices to an existing system to accommodate a tenant remodel. There are no initiating devices part of this permit scope of work.

Associated building permit: BLD10-01858 (ST. LUKE'S BUISNESS CENTER - Shoreline Tech Center - Workmen's Comp Center) Permit is to remodel an existing open office area to now include modular furniture. Approval contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing wall to provide data to all new work stations, installation of new pre-manufactured furniture equipment, relocate existing lighting, installation of new mechanical, installation of electrical, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  12/2/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection10/12/201010/12/201010/13/2010PPASS
DetailsForrest France
Fire alarm testing per the scope of work passed field inspection. Contractor to provide record of completion report as discussed.
Issue and Print Permit  10/5/2010 DONE
Plan assigned to (Stephanie)9/29/2010 10/1/2010 DONE
DetailsStephanie L. Cobbley
Telephone call  10/1/2010 DONE
Left a message at the office of Fire Sentry Systems as well as on John Lopez's cell phone regarding the information needed for the candela ratings of two existing notification devices affected by this tenant remodel.
1st review completed  10/1/2010 DONE
Telephone call  10/1/2010 DONE
Earl from Fire Sentry called to let me know the existing notification devices in question are 110cd.
Alarm Plan Check10/1/2010 10/1/2010 PASS
DetailsStephanie L. Cobbley
Plans approved - see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  10/1/2010 DONE
Approved redlined plans available at front counter
Inspection Record Card- Fire10/1/2010 10/1/2010 DONE
DetailsPatricia Smith
Telephone call  10/1/2010 DONE
t/c w earl at ###-#### - permit ready and fees given
Permit Ready to Issue  10/1/2010 DONE
Details
Miscellaneous action  9/30/2010 DONE
Waiting on information from Earl L. at Fire Sentry Systems on the actual candela ratings of the existing notification devices just outside the remodeled areas.
Application received  9/29/2010