Miscellaneous action | | | 12/21/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 12/13/2010 | 12/14/2010 | 12/14/2010 | A | PASS |
Forrest France
|
|
|
Noted corrections finished, fire alarm work passed functional testing. Permit finaled.
|
INSP-Final Inspection | 12/9/2010 | 12/10/2010 | 12/10/2010 | A | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for the locations of the deficiencies. They include adding a/v coverage in Offices 105 and 106, providing coverage at the end of a corridor where an existing a/v had been removed, relocating a smoke detector located too close to a supply air diffuser, and setting the correct candella for a strobe in the Vontrol Room on the existing side of this building. No devices were tested. Per plan review as-builts can be provided for the changes.
|
INSP-Conference | 12/9/2010 | 12/9/2010 | 12/9/2010 | P | DONE |
Forrest France
|
|
|
Regarding sync issues at notification zones per NFPA 72 6.8.5.3.
|
CHANGE STATUS TO (ISS) | | | 11/18/2010 | | DONE |
Barbara Stitt
|
|
|
|
(F) Reprint permit | | | 11/18/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 11/9/2010 | | 11/16/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 11/16/2010 | | 11/16/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved with redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 11/16/2010 | | DONE |
|
|
|
Approved redlined plan modification plans available at front counter.
|
Inspection Record Card- Fire | 11/16/2010 | | 11/16/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/16/2010 | | DONE |
|
|
|
t/c w kevin perez - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 11/16/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/9/2010 | | DONE |
Tisha Gallop
|
|
|
Plan Modification: received two copies of application, submittal documents and plans; routed to SLC.
|
Plan assigned to (Stephanie) | 10/4/2010 | | 10/11/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 10/4/2010 | | 10/11/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 10/11/2010 | | DONE |
|
|
|
Spoke to Kevin Perez with Mountain Power Electric regarding redlines and review comments. I let him know that I would need to either reject them now (thus only one review fee upon resubmittal approval), or I could approve them with the understanding a plan modification will be required to be submitted and approved prior to calling for a final inspection (additional review fees will apply). Kevin said he'd rather pay the additional fees so he can begin work on the project.
|
1st review completed | | | 10/11/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 10/11/2010 | | 10/11/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plans approved with review comments and redlines. A plan modification is required prior to calling for a final inspection.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/11/2010 | | DONE |
|
|
|
Approved redlined plans available at front counter.
|
Inspection Record Card- Fire | 10/11/2010 | | 10/11/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/11/2010 | | DONE |
|
|
|
t/c w kevin at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/11/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/11/2010 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 10/4/2010 | | |
|
|
|
|