Miscellaneous action | | | 2/9/2011 | | DONE |
|
|
|
|
INSP-Final Inspection | 1/7/2011 | 1/10/2011 | 1/10/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 | P | FAIL |
Troy Cobbley
|
|
|
The horns and strobes did not sync. All other items were ok including the end of line voltage.
|
INSP-Final Inspection | 10/29/2010 | 11/2/2010 | 11/2/2010 | A | FAIL |
Troy Cobbley
|
|
|
Relocate the two smoke detectors in the warehouse to the deck. Relocate three smoke detectors in the office area away from the supply registers. No testing was performed. As builts need to be provided showing the 12 guage wire used in the notification circuit and the correction of the plan reviewers redline comments.
|
Issue and Print Permit | | | 10/18/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 10/8/2010 | | 10/12/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 10/12/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 10/12/2010 | | 10/12/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 10/12/2010 | | DONE |
|
|
|
Approved redlined plans available at front counter
|
Inspection Record Card- Fire | 10/12/2010 | | 10/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/12/2010 | | DONE |
|
|
|
t/c w mike at 32301199 - permit ready and fees given
|
Permit Ready to Issue | | | 10/12/2010 | | DONE |
|
|
|
|
Application received | | | 10/8/2010 | | |
|
|
|
|