Miscellaneous action | | | 6/8/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/23/2011 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 3/10/2011 | 3/10/2011 | 3/10/2011 | P | PASS |
Troy Cobbley
|
|
|
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
|
INSP-Sprinkler Rough-in/Hydro | 3/10/2011 | 3/10/2011 | 3/10/2011 | P | PART |
Forrest France
|
|
|
Dry system hydrostatic and pneumatic testing passed- see activity notes under project related FIR10-00579.
|
FIR-Aging Inspection | 1/25/2011 | 1/25/2011 | 2/2/2011 | | NR |
Troy Cobbley
|
|
|
Wip
|
INSP-Sprinkler Rough-in | 11/12/2010 | 11/15/2010 | 11/16/2010 | A | PART |
Forrest France
|
|
|
New dry system piping at the cricket passed rough-in inspection. Two obstruction issues repaired while on site. See approved plan annotation for one area -the "entry element" not yet built including one dry pendent head and an upright not installed.
|
Sprinkler Plan Check | 10/19/2010 | | 10/19/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/19/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 10/19/2010 | | 10/19/2010 | | DONE |
Darla L Downs
|
|
|
|
Permit Ready to Issue | | | 10/19/2010 | | DONE |
|
|
|
|
Telephone call | | | 10/19/2010 | | |
|
|
|
10-19-10 called permit ready ///dld
|
Issue and Print Permit | | | 10/19/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Tim) | 10/13/2010 | | 10/19/2010 | | DONE |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 10/18/2010 | | DONE |
|
|
|
received 3 sets of plans /applications sent to Tim Frost for review ///dld
|
Sprinkler Plan Check | 10/15/2010 | | 10/15/2010 | | FAIL |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 10/15/2010 | | DONE |
Tim Frost
|
|
|
|
Miscellaneous action | | | 10/15/2010 | | DONE |
|
|
|
Emailed review to contractor
|
Telephone call | | | 10/15/2010 | | DONE |
|
|
|
t/c w jeff anderson at ###-#### - permit denied - needs to be picked up and resubmitted
|
Application received | | | 10/13/2010 | | DONE |
Barbara Stitt
|
|
|
|
Case Summary | | | 10/13/2010 | | DONE |
Barbara Stitt
|
|
|
|