Miscellaneous action | | | 2/9/2011 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 2/1/2011 | 2/3/2011 | 2/3/2011 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
(F) Reprint permit | | | 11/18/2010 | | DONE |
Barbara Stitt
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/18/2010 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 11/17/2010 | | 11/17/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/17/2010 | | DONE |
|
|
|
t/c w bryan - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 11/17/2010 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 11/9/2010 | | 11/16/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
Plan Modification
|
Alarm Plan Check | 11/16/2010 | | 11/16/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Plan modification approved
|
PLANS TAKEN FRONT DESK ALARM | | | 11/16/2010 | | DONE |
|
|
|
Approved plan modification plans available at front counter
|
Plan resubmittals received | | | 11/9/2010 | | |
Barbara Stitt
|
|
|
PLan Modification
|
Case Summary | | | 11/9/2010 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 11/3/2010 | | DONE |
Barbara Stitt
|
|
|
Left message for Don that permit is ready and fees due on 11-3-10 @ 8:25am
|
Issue and Print Permit | | | 11/3/2010 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Stephanie) | 10/18/2010 | | 11/2/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 11/2/2010 | | 11/2/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
approved - see redlines and review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 11/2/2010 | | DONE |
|
|
|
approved plans available at front counter
|
Inspection Record Card- Fire | 11/2/2010 | | 11/2/2010 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 11/2/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/26/2010 | | DONE |
Tisha Gallop
|
|
|
received application and two copies of submittal folder and plans; taken to Fire Review
|
Telephone call | | | 10/22/2010 | | DONE |
|
|
|
Spoke to Bret with Mountain Alarm regarding wattage calculations that were not provided. I let him know he will need to provide wattage calculations indicating the system is within the existing amplifier capacity and agreed that the calculations can be provided at the time of inspection rather than in the resubmittal. Due to limited existing information available, I told Bret I would accept 'estimated' wattage calculations based on all of the existing speakers being tapped at .5 watt, with the exception of the basement conference rooms, which should be estimated to be at 1 watt. I told him if the 'estimated' values put him over the available 100 Watts, that he would need to either get the exact values or provide a new amplifier for the new speakers.
|
Telephone call | | | 10/22/2010 | | DONE |
|
|
|
I called Bret at Mountain Alarm to let him know I would be rejecting the plans. We briefly went over the discrepencies. I told him they redlined plans and submittals would be available at the front desk for him to pick up.
|
1st review completed | | | 10/22/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 10/22/2010 | | 10/22/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
Plans denied - see review comments and redlined plans
|
Miscellaneous action | | | 10/22/2010 | | DONE |
|
|
|
Plans placed at front counter for contractor pick up
|
Application received | | | 10/18/2010 | | |
|
|
|
|