Permit NumberFIR10-00521
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1055 N CURTIS RD
Project NameSARMC BMAC ELEVATOR RECALL
Customer Number 
ePlanReviewNo
Description
This quick permit is to provide elevator recall functions for elevator #1 & #2. Per the contractor, this building is not sprinklered, and there are no fireman's hat light functions available. Seven smoke detectors and four control zams are being added to the existing fire alarm system. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/14/2013 DONE
Plans taken to records for scanning
INSP-Final Inspection1/15/20131/16/20131/16/2013APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection1/14/20131/14/20131/15/2013 NR
DetailsTroy Cobbley
FIR-Aging Inspection9/24/20129/24/201210/1/2012 NR
DetailsTroy Cobbley
Forwarded information to Scott for further action.
FIR-Aging Inspection4/26/20124/26/20125/2/2012 NR
DetailsTroy Cobbley
Charlie is going to schedule Dante to finishs the as-builts.
FIR-Aging Inspection1/20/20121/20/20121/23/2012 NR
DetailsTroy Cobbley
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR-Aging Inspection4/27/20114/27/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
INSP-Final Inspection2/10/20112/16/20112/16/2011AFAIL
DetailsTroy Cobbley
Provide signage at the inoperative firemans controls in both elevators as discussed or make all functions operational.
INSP-Final Inspection1/28/20112/9/20112/9/2011ACANC
DetailsTroy Cobbley
The contractor did not have the city approved job site copy plans on site. No inspection was performed.
Telephone call  1/14/2011 DONE
Brian with SimplexGrinnel called to discuss the elevator alternate recall. Per Brian, the elevator is not capable of doing alternate recall, so he wanted to know A) what documentation we needed (i.e. as-built vs. plan modification); and B) what to do with the smoke detector on the 1st floor (i.e. remove it, program it for something else etc..). He proposed leaving the modules for the alternate recall in case the elevator is eventually upgraded. I agreed and asked him to provide as-built drawings (2 sets) with a new one-line indicating those modules are for 'future' alternate recall and a revised matrix with a note or indication that the elevator is not capable of alternate recall but leave the function there for 'future use'. He then proposed to have the 1st floor smoke detectors wired to the modules just not programmed for recall yet. I told him that would be fine as long as it is noted somewhere on the drawings that it is currently programmed for general building alarm but is wired up for alternate recall pending future elevator upgrades.
Plan assigned to (Stephanie)10/21/2010 10/25/2010 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)10/21/2010 10/25/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  10/25/2010 DONE
Alarm Plan Check10/25/2010 10/25/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  10/25/2010 DONE
Approved quick permit documents available at front counter
Inspection Record Card- Fire10/25/2010 10/25/2010 DONE
DetailsPatricia Smith
Telephone call  10/25/2010 DONE
left vm for charlie at ###-#### - permit ready and fees given
Permit Ready to Issue  10/25/2010 DONE
Details
Issue and Print Permit  10/25/2010 DONE
DetailsBarbara Stitt
Application received  10/21/2010