Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR10-00522
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE AVE Unit: 1081
Project NameBTS - #1081, Bare Escentuals
Customer Number 
ePlanReviewNo
Description
The Fire Sprinkler Scope of work consists of adding and relocating sprinklers to accommodate new wall and ceiling configuration.


Building Department Scope:

To remodel an existing 1,264 sq. ft. "vanilla shell & core" space for use as retail sales & support areas, for new tenant "Bare Essentials". Work includes construction of interior non-combustible frame walls to create the sales floor, storage room and accessible staff restroom; construction of engineered structural support for new storefront, display areas & roll down security grill; interior millwork, floor, wall & ceiling finishes; and electrical, plumbing, mechanical, sprinkler & alarm system modifications for new tenant. This building is fully sprinklered. Any alterations to the sprinkler or alarm system require separate application, plans and permits before work can commence and shall be in accordance with applicable NFPA Standards as regulated by the fire department. The smoke evacuation system shall remain operational as originally designed and installed under the 1985 UBC. Racking that exceeds 8 ft. in height requires a separate applications, engineering design calcs and details and floor plan for a building permit before installation. drs

Fire Sprinkler System Design/Spacing:

Hydraulics were neither supplied nor required. For the most part the sprinklers are being relocated on a one for one basis. There is one new branch line being cut into the existing 3” main to fees two new sprinklers in the entrance soffit. The existing systems is a 3”x3”x1¼” grid
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  1/14/2011 DONE
Sent to records for scanning.
INSP-Final Inspection11/18/201011/19/201011/19/2010PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in11/2/201011/2/201011/2/2010PPASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover.
Plan assigned to (Tim)10/21/2010 10/26/2010 DONE
DetailsTim Frost
Sprinkler Plan Check10/26/2010 10/26/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  10/26/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  10/26/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire10/26/2010 10/26/2010 DONE
DetailsPatricia Smith
Telephone call  10/26/2010 DONE
t/c w brodie at ###-#### - permit ready and fees given
Permit Ready to Issue  10/26/2010 DONE
Details
Issue and Print Permit  10/26/2010  
Application received  10/21/2010  
Case Summary  10/21/2010 DONE