Permit Information
Permit NumberFIR10-00527
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 12435 W USTICK RD
Project NameUSTICK ELEMENTARY - IPDACT
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide and IPDACT internet communicator for the existing fire alarm system and a duct detector for HVAC shut down for the unit in the kitchen/Gym area to comply with requirements of BLD08-01564.

Associated building permit: BLD08-01564 ** (Ustick Elementary School) ** (HVAC Installation) ** To install new 10 ton HVAC unit on existing roof structure of the Gym per plans and attached engineering. Work to include, construction of new curb to mount unit, to be centered over the existing roof beam, no structural modifications to the existing structure required. RmH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  10/13/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/13/20119/13/20119/13/2011PPASS
DetailsTroy Cobbley
permit finaled
INSP-Alarm Testing9/12/20119/13/20119/13/2011ADONE
DetailsTroy Cobbley
Testing is done. Wrong inspection type called in.
INSP-Final Inspection4/14/20114/15/20114/15/2011PFAIL
DetailsTroy Cobbley
Provide map at the facp. All other items ok.
Issue and Print Permit  12/8/2010 DONE
DetailsBarbara Stitt
Alarm Plan Check11/30/2010 11/30/2010 PASS
DetailsStephanie L. Cobbley
approved - see review comments
PLANS TAKEN FRONT DESK ALARM  11/30/2010 DONE
approved plans available at front counter
Inspection Record Card- Fire11/30/2010 11/30/2010 DONE
DetailsPatricia Smith
Telephone call  11/30/2010 DONE
t/c w john - permit ready and fees given
Permit Ready to Issue  11/30/2010 DONE
Details
Plan assigned to (Stephanie)10/22/2010 11/30/2010 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  11/24/2010  
DetailsBarbara Stitt
Case Summary  11/24/2010  
DetailsBarbara Stitt
Alarm Plan Check11/19/2010 11/19/2010 FAIL
DetailsStephanie L. Cobbley
Plans denied - see review comments
Telephone call  11/19/2010 DONE
Spoke to John L. at FSS to let him know the plans were being denied and why. I let him know his set of plans would be at the front counter for pick-up.
Miscellaneous action  11/19/2010 DONE
Denied plans available at front counter
Telephone call  11/17/2010 DONE
Spoke with John at FSS to let him know I need a floorplan showing the actual location of the duct detector - it is not acceptable to show the device in a general area on the site plan.
Plan resubmittals received  11/15/2010 DONE
DetailsTisha Gallop
received two copies of application, submittal folder and plans; taken to SLC
Alarm Plan Check11/10/2010 11/10/2010 FAIL
DetailsStephanie L. Cobbley
No written review comments. Plans denied. Contractor is going to resubmit with a duct detector added to comply with a previous building permit requirement (BLD08-01564).
Miscellaneous action  11/10/2010 DONE
Denied plans available at front counter
1st review completed  11/5/2010 DONE
Telephone call  11/5/2010 DONE
Spoke to John with Fire Sentry to let him know I can not approve the fire alarm plans because there is an open building permit (BLD08-01564) that needs to be finaled first. That building permit was not finaled because under the permit a 10-ton HVAC unit was installed over the gym with a duct detector that needs to be tied in to the existing fire alarm system. A fire permit for that work has never been pulled. I explained to John that that will need to be addressed before I can pass this permit. I let him know it could be done under a separate permit, or I could fail this one and he could resubmit with the duct detector work so only one review fee would apply. I also let John know that, while it was approved under the original permit to allow the main building and portable building to have two independent fire alarm systems, it would be highly recommended to tie in the panels so that the main panel could monitor alarm, trouble, and supervisory functions of the portable's panel. I reiterated that the 'tie-in' would not be a required issue or hold up this permit due to previous agreements, but that for public safety reasons it really should be done. He stated he would let me know next week which route they'd like to take.
Application received  10/22/2010