INSP-Final Inspection | 3/23/2011 | 3/24/2011 | 3/24/2011 | P | PASS |
Forrest France
|
|
|
Field verified adjustments, inspection passed. Permit finaled.
|
FIR-Aging Inspection | 3/22/2011 | 3/22/2011 | 3/23/2011 | | PART |
Forrest France
|
|
|
|
FIR-Aging Inspection | 1/13/2011 | 1/13/2011 | 1/13/2011 | | PEND |
Forrest France
|
|
|
Ref. activity notes 11/9/10
|
INSP-Final Inspection | 11/8/2010 | 11/9/2010 | 11/9/2010 | P | FAIL |
Forrest France
|
|
|
Pendent heads at some locations are obstructed by close proximity to adjacent ductwork affecting pattern development.
|
1st review completed | | | 10/28/2010 | | DONE |
Troy Cobbley
|
|
|
|
Sprinkler Plan Check | 10/28/2010 | | 10/28/2010 | | PASS |
Troy Cobbley
|
|
|
Per field review and inspection.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/28/2010 | | DONE |
Troy Cobbley
|
|
|
|
Issue and Print Permit | | | 10/28/2010 | | DONE |
|
|
|
per trf
|
Plan assigned to (Scott) | | | 10/27/2010 | | DONE |
Bill Alexander
|
|
|
This permit was created on the web by Paul Marcolina
|
Application received | | | 10/27/2010 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|