Miscellaneous action | | | 1/14/2011 | | DONE |
|
|
|
Sent to records for scanning.
|
INSP-Sprinkler Rough-in | 11/22/2010 | 11/23/2010 | 11/23/2010 | A | PASS |
Forrest France
|
|
|
Forward flow test completed satisfactory. Fire sprinkler permit finaled.
|
INSP-Final Inspection | 11/19/2010 | 11/22/2010 | 11/22/2010 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit okay for final pending satisfactory forward flow test. PRV installed while on site.
|
INSP-Sprinkler Rough-in/Hydro | 11/19/2010 | 11/22/2010 | 11/22/2010 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test completed satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2010 | 11/16/2010 | 11/16/2010 | A | PART |
Forrest France
|
|
|
Overhead rough-in inspection for the scope of work completed acceptable. PRV to be added post hydrostatic testing- see review notes. Discussed hydro test schedule.
|
INSP-Sprinkler Rough-in | 11/15/2010 | 11/15/2010 | 11/16/2010 | P | DEFR |
Forrest France
|
|
|
|
Plan assigned to (Tim) | 10/29/2010 | | 11/10/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/10/2010 | | 11/10/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 11/10/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/10/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 11/10/2010 | | 11/10/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/10/2010 | | DONE |
|
|
|
t/c w shelly - permit ready and fees given
|
Permit Ready to Issue | | | 11/10/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/10/2010 | | DONE |
Barbara Stitt
|
|
|
|
Miscellaneous action | | | 11/9/2010 | | DONE |
|
|
|
Spoke with Steve Trout and explained what the lower level design criteria as submitted could be use to protect per NFPA 13 definition for Ordinary Hazard Group I.
|
Miscellaneous action | | | 11/5/2010 | | DONE |
|
|
|
Spoke with the architect. He explained that the entire lower level is not being used for paper storage as described on the owners certificate. He said that there would be a small amount of paper storage and furniture storage. I told him to sendn in a new owners certifcate.
|
Miscellaneous action | | | 10/30/2010 | | DONE |
|
|
|
Requested a new owners certificate.
|
Application received | | | 10/29/2010 | | |
|
|
|
|