Permit Information
Permit NumberFIR10-00557
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 11311 W CHINDEN BLVD
Project NameHP BLDG 1 TEN FOCUS ROOMS
Customer Number 
ePlanReviewNo
Description
This quick permit is to add ten strobes to go in each of ten new focus rooms. These devices are to be tied in to existing notification circuits. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There are no written review comments. Associated building permit: BLD10-02388 (HEWLETT PACKARD BLDG 1 - 1ST & 2ND FLOOR) This building is fully sprinklered for unlimited allowable area increase. Remodel of 528 sq. ft. consisting of four existing staff support areas on the first level, each less than 250 sq. ft., dividing one room into two smaller rooms, a new total of five rooms to be used as Small Conference & Focus rooms for specific staff work areas; remodel of 603 sq. ft. consisting of six existing staff support areas of less than 250 sq. ft. each, on the second level, dividing one room to become two rooms for a new total of seven rooms for use as Small Conference & Focus rooms as specific staff work areas. Work includes select interior demolition, construction of non-combustible frame walls, drywall cover, suspended ceiling grid modification, interior finishes, millwork, electrical, mechanical, sprinkler and alarm systems modifications, all per reviewed plans to include notes on plans and all attached plan review conditions and comments for all reviewing agencies. This scope of wotk will not increase building area, change occupancy use group(s) or increase the occupant load for this building. Separate applications, plans and permits are required before any work can begin on the sprinkler or alarm systems, as regulated by the fire department. drs.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection12/27/201012/29/201012/29/2010APASS
DetailsForrest France
Scope of fire alarm work passed inspection, permit finaled.
Issue and Print Permit  11/8/2010 DONE
1st review completed  11/5/2010 DONE
Alarm Plan Check11/5/2010 11/5/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  11/5/2010 DONE
Approved quick permit plans available at front counter
Permit Ready to Issue  11/5/2010 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire11/5/2010 11/5/2010 DONE
DetailsBarbara Stitt
Telephone call  11/5/2010 DONE
DetailsBarbara Stitt
Left voice message for Charlie that permit is ready & fees due on 11-5-10 @ 4:25pm
Application received  11/4/2010  
Plan assigned to (Stephanie)11/4/2010 11/4/2010 DONE
DetailsStephanie L. Cobbley