Miscellaneous action | | | 12/2/2010 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 11/12/2010 | 11/15/2010 | 11/15/2010 | A | PASS |
Forrest France
|
|
|
Fire alarm work passed site inspection. Permit finaled.
|
Alarm Plan Check | 11/12/2010 | | 11/12/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved with conditions - no written review comments. See project activity notes.
|
PLANS TAKEN FRONT DESK ALARM | | | 11/12/2010 | | DONE |
|
|
|
approved quick permit plans available at the front counter.
|
Inspection Record Card- Fire | 11/12/2010 | | 11/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Permit Ready to Issue | | | 11/12/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/12/2010 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 11/12/2010 | | DONE |
|
|
|
customer was up front when permit was processed
|
1st review completed | | | 11/10/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 11/10/2010 | | 11/10/2010 | | FAIL |
Stephanie L. Cobbley
|
|
|
This quick permit is denied. The hood suppression system monitoring is required to be on it's own zone (per 2006 IFC 907.9.2 and 2007 NFPA 72). There are no written review coments.
|
Plan resubmittals received | | | 11/10/2010 | | DONE |
|
|
|
|
Application received | | | 11/8/2010 | | |
|
|
|
|
Plan assigned to (Stephanie) | 11/8/2010 | | 11/8/2010 | | DONE |
Darla L Downs
|
|
|
|