INSP-Final Inspection | 12/2/2010 | 12/3/2010 | 12/3/2010 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 11/22/2010 | 11/22/2010 | 11/22/2010 | P | PART |
Troy Cobbley
|
|
|
Per conversation with EKC and the building inspector the sprinkler piping over the restrooms can be covered.
|
INSP-Sprinkler Rough-in | 11/19/2010 | 11/22/2010 | 11/22/2010 | A | FAIL |
Troy Cobbley
|
|
|
The insulation issue has not been addressed. Sprinkler piping can not be covered.
|
Plan assigned to (Tim) | 11/18/2010 | | 11/19/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/19/2010 | | 11/19/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/19/2010 | | DONE |
Tim Frost
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/19/2010 | | DONE |
|
|
|
no fees due - change to issue status per trf
|
INSP-Sprinkler Rough-in | 11/17/2010 | 11/18/2010 | 11/18/2010 | A | FAIL |
Troy Cobbley
|
|
|
Resubmitt both plans due to: the floor plans don't match the actual wall layout, the site plan and addresses don't match, sprinkler heads used don't match whats installed. Also the insulation located at the deck is creating obstructions the the upright sprinkler heads. A 1" minimum clearance is required per NFPA 13.
|
Plan resubmittals received | | | 11/18/2010 | | DONE |
|
|
|
plan mod received
|
Plan assigned to (Tim) | 11/10/2010 | | 11/12/2010 | | DONE |
Tim Frost
|
|
|
|
Sprinkler Plan Check | 11/12/2010 | | 11/12/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are NO annotations on the plans.
|
1st review completed | | | 11/12/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/12/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 11/12/2010 | | 11/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/12/2010 | | DONE |
|
|
|
left vm for cameron - permit ready and fees given
|
Permit Ready to Issue | | | 11/12/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 11/12/2010 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 11/10/2010 | | |
|
|
|
|