Permit Information
Permit NumberFIR10-00573
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 4628 W STATE ST
Project NameVanilla TI-
Customer Number 
ePlanReviewNo
Description
Quick Permit
Add one sprinkler and relocate one sprinkler due to a new bathroom

(Vanilla Finish – Collister Shopping Center) Permit is to Remodel an existing 2,755 square foot retail space to provide separate sex restrooms and all other required fixtures. Approval contingent upon adhering to the approved plans on file. Work to include: construction of interior non-bearing walls to create separate sex accessible restrooms, installation of new high / low drinking fountain, installation of new mop sink, and finishes in compliance with chapter 8 of the 2006 IBC. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. An additional permit is required prior to occupying this tenant space. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/2/201012/3/201012/3/2010PPASS
DetailsTroy Cobbley
Permit finaled.
INSP-Sprinkler Rough-in11/22/201011/22/201011/22/2010PPART
DetailsTroy Cobbley
Per conversation with EKC and the building inspector the sprinkler piping over the restrooms can be covered.
INSP-Sprinkler Rough-in11/19/201011/22/201011/22/2010AFAIL
DetailsTroy Cobbley
The insulation issue has not been addressed. Sprinkler piping can not be covered.
Plan resubmittals received  11/19/2010  
DetailsBarbara Stitt
INSP-Sprinkler Rough-in11/17/201011/18/201011/18/2010AFAIL
DetailsTroy Cobbley
Resubmitt both plans due to: the floor plans don't match the actual wall layout, the site plan and addresses don't match, sprinkler heads used don't match whats installed. Also the insulation located at the deck is creating obstructions the the upright sprinkler heads. A 1" minimum clearance is required per NFPA 13.
Issue and Print Permit  11/16/2010 DONE
Plan assigned to (Tim)11/10/2010 11/12/2010 DONE
DetailsTim Frost
Sprinkler Plan Check11/12/2010 11/12/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  11/12/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  11/12/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire11/12/2010 11/12/2010 DONE
DetailsPatricia Smith
Telephone call  11/12/2010 DONE
left vm for cameron - permit ready and fees given
Permit Ready to Issue  11/12/2010 DONE
Details
Application received  11/10/2010