Permit Information
Permit NumberFIR10-00577
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 1150 N CURTIS RD
Project NameUS BUREAU OF REC - CONF RM
Customer Number 
ePlanReviewNo
Description
10/5/11 PLAN MODIFICATION (0 initiating devices affected): This plan modification is to relocate and increase the candela rating of a notification device in a conference room that has been resized since the original review. There are no additional review comments. 11/12/10:This quick permit is to provide door holders, associated smoke detectors for release of the door holders, and a notification device to a conference room close to the main entry area. The new devices are being added to the existing Simplex 4020 panel existing circuits. There are no written review comments. Approval is subject to field measurement of the EOL voltage drop. For appliances with an operating voltage range of 16V – 33V, the minimum acceptable voltage is 19.6V with the AC power off. Any measurement below this voltage will be considered insufficient to run the NACs at the end of useful battery life of 20.4V. UL 864, Standard for Control Units for Fire Signaling Systems. The installing contractor shall have available at final inspection a voltage meter and measure end of line voltages; witnessed by the field inspector. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/1/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection5/16/20125/17/20125/17/2012APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/11/20125/16/20125/16/2012AFAIL
DetailsTroy Cobbley
I went ahead and tested the horn/strobe and the smoke detectors for the door release. The devices functioned correctly and the signals received at the central station. The smoke detectors have been centered at the doors. What is not complete are the plans. Per the original correction notice plans needed to be re-submitted or as-builts provided showing the 30cd strobe. The fire alarm vendor chose to re-submit for a plan modification. The problem is the plan modifications show a 110cd strobe where the 30cd has been installed. Also the room size is incorrect and the actual location of the work is in the south end of the building not as shown in the north end of the building. As discussed an accurate as-built package needs to be provided prior to a final sign off.
FIR-Aging Inspection4/18/20124/18/20124/18/2012 NR
DetailsTroy Cobbley
I spoke to Charlie with Simplex several weeks ago and he stated that they were working on this permit.
Issue permit  10/6/2011 DONE
Payment received via Govolutions
Miscellaneous action  10/6/2011 DONE
DetailsTisha Gallop
picked up plans
Plan assigned to (Stephanie)9/27/2011 10/5/2011 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check10/5/2011 10/5/2011 PASS
DetailsStephanie L. Cobbley
Quick permit plan modification approved - no written review comments.
PLANS TAKEN FRONT DESK ALARM  10/5/2011 DONE
Approved quick permit plan modification documents available at front counter.
Inspection Record Card- Fire10/5/2011 10/5/2011 DONE
DetailsPatricia Smith
Telephone call  10/5/2011 DONE
left vm for dante - permit ready (plan mod) and fees given
Permit Ready to Issue  10/5/2011 DONE
Details
Plan resubmittals received  9/27/2011 DONE
DetailsTisha Gallop
PLAN MODIFICATION: received two copies application, submittal folder; routed to fire review.
FIR-Aging Inspection5/2/20115/2/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
INSP-Final Inspection1/28/20112/9/20112/9/2011AFAIL
DetailsTroy Cobbley
The smoke detectors for door release shall be centered on the doorway. Also plans will either need to be resubmitted showing the 30cd strobe or as-builts with verification of EOL voltage drop.
Issue and Print Permit  11/19/2010 DONE
DetailsBarbara Stitt
Application received  11/12/2010  
Plan assigned to (Stephanie)11/12/2010 11/12/2010 DONE
DetailsStephanie L. Cobbley
Plan assigned to (Stephanie)11/12/2010 11/12/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  11/12/2010 DONE
Alarm Plan Check11/12/2010 11/12/2010 PASS
DetailsStephanie L. Cobbley
Quick permit approved - no written review comments
PLANS TAKEN FRONT DESK ALARM  11/12/2010 DONE
quick permit approved plans available at front counter
Inspection Record Card- Fire11/12/2010 11/12/2010 DONE
DetailsPatricia Smith
Telephone call  11/12/2010 DONE
left vm for charlie - permit ready and fees given
Permit Ready to Issue  11/12/2010 DONE
Details