Miscellaneous action | | | 6/1/2012 | | DONE |
|
|
|
Plans taken to records for scanning.
|
INSP-Final Inspection | 5/16/2012 | 5/17/2012 | 5/17/2012 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/11/2012 | 5/16/2012 | 5/16/2012 | A | FAIL |
Troy Cobbley
|
|
|
I went ahead and tested the horn/strobe and the smoke detectors for the door release. The devices functioned correctly and the signals received at the central station. The smoke detectors have been centered at the doors. What is not complete are the plans. Per the original correction notice plans needed to be re-submitted or as-builts provided showing the 30cd strobe. The fire alarm vendor chose to re-submit for a plan modification. The problem is the plan modifications show a 110cd strobe where the 30cd has been installed. Also the room size is incorrect and the actual location of the work is in the south end of the building not as shown in the north end of the building. As discussed an accurate as-built package needs to be provided prior to a final sign off.
|
FIR-Aging Inspection | 4/18/2012 | 4/18/2012 | 4/18/2012 | | NR |
Troy Cobbley
|
|
|
I spoke to Charlie with Simplex several weeks ago and he stated that they were working on this permit.
|
Issue permit | | | 10/6/2011 | | DONE |
|
|
|
Payment received via Govolutions
|
Miscellaneous action | | | 10/6/2011 | | DONE |
Tisha Gallop
|
|
|
picked up plans
|
Plan assigned to (Stephanie) | 9/27/2011 | | 10/5/2011 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | 10/5/2011 | | 10/5/2011 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit plan modification approved - no written review comments.
|
PLANS TAKEN FRONT DESK ALARM | | | 10/5/2011 | | DONE |
|
|
|
Approved quick permit plan modification documents available at front counter.
|
Inspection Record Card- Fire | 10/5/2011 | | 10/5/2011 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 10/5/2011 | | DONE |
|
|
|
left vm for dante - permit ready (plan mod) and fees given
|
Permit Ready to Issue | | | 10/5/2011 | | DONE |
|
|
|
|
Plan resubmittals received | | | 9/27/2011 | | DONE |
Tisha Gallop
|
|
|
PLAN MODIFICATION: received two copies application, submittal folder; routed to fire review.
|
FIR-Aging Inspection | 5/2/2011 | 5/2/2011 | 5/5/2011 | | NR |
Troy Cobbley
|
|
|
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
|
INSP-Final Inspection | 1/28/2011 | 2/9/2011 | 2/9/2011 | A | FAIL |
Troy Cobbley
|
|
|
The smoke detectors for door release shall be centered on the doorway. Also plans will either need to be resubmitted showing the 30cd strobe or as-builts with verification of EOL voltage drop.
|
Issue and Print Permit | | | 11/19/2010 | | DONE |
Barbara Stitt
|
|
|
|
Application received | | | 11/12/2010 | | |
|
|
|
|
Plan assigned to (Stephanie) | 11/12/2010 | | 11/12/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan assigned to (Stephanie) | 11/12/2010 | | 11/12/2010 | | DONE |
Stephanie L. Cobbley
|
|
|
|
1st review completed | | | 11/12/2010 | | DONE |
|
|
|
|
Alarm Plan Check | 11/12/2010 | | 11/12/2010 | | PASS |
Stephanie L. Cobbley
|
|
|
Quick permit approved - no written review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 11/12/2010 | | DONE |
|
|
|
quick permit approved plans available at front counter
|
Inspection Record Card- Fire | 11/12/2010 | | 11/12/2010 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 11/12/2010 | | DONE |
|
|
|
left vm for charlie - permit ready and fees given
|
Permit Ready to Issue | | | 11/12/2010 | | DONE |
|
|
|
|