Permit Information
Permit NumberFIR10-00599
StatusFinaled
Name PEAK ALARM
Site Address 276 W BOBWHITE CT
Project NameBarbacoa Restaurant
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to provide a required manual fire alarm system in a new sprinklered building. This permit scope is to include a pull station, notification throughout the building, monitoring of three kitchen hood systems, monitoring the sprinkler system, and duct detector monitoring (the duct detectors shown are conventional and are being provided by others). Also included in the permit is customer requested monitoring of the Knox box and a customer requested exterior horn/strobe.
Associated building permit: BLD10-00550 Barbacoa Restaurant Rebuild and Addition - To rebuild an 8,170 square foot, one story, wood framed restaurant building that was destroyed by fire. The building is being reconstructed from the existing foundation up. There will also be a new 310 square foot main entry area addition on the west side of the building and a new 795 square foot addition along the south side of the building. The roof height will be increased approximately 8 feet above the original building roof height. The original approved plans are being modified to include a 400 square foot, mezzanine above the public restroom area and a 500 square foot dining area on the north east corner of the roof. The mezzanine is limited to 20 seats and the roof top dining is limited to 29 seats. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection12/28/201012/29/201012/29/2010APASS
DetailsForrest France
C/N items finished, re-inspection passed. Final okay pending scanable as-built record drawings are provided including an accurate map at the panel.
INSP-Final Inspection12/27/201012/27/201012/28/2010PPART
DetailsForrest France
Adjustments for final include; provide as-built drawings accurately reflecting field installation including duct detectors at RTUs 5 and 7, the deletion of one KH monitor, provide a strobe only at the wine/av room, amend visual coverage at lounge 108 due to obstruction by ceiling suspended finishes, provide a lock at the FACP circut breaker, post accurate map at the panel. Remainder of fire alarm work tested satisfactory.
INSP-Final Inspection12/8/201012/9/201012/9/2010APART
DetailsForrest France
Hood suppression and fire sprinkler riser system interconnections tested okay, offsite monitoring verified. Minor corrections and account information adjustments done while on site.
Issue and Print Permit  12/2/2010 DONE
DetailsBarbara Stitt
Plan assigned to (Stephanie)11/24/2010 12/1/2010 DONE
DetailsStephanie L. Cobbley
Telephone call  12/1/2010 DONE
Jeff with e2co returned my call and gave me the information I requested.
Telephone call  12/1/2010 DONE
Spoke with Ben Jackson at Peak Alarm to ask about the duct detectors. There were no data sheets provided for the duct detectors or addressable relay modules indicated for the HVAC shutdown, only monitor modules going to the duct detectors. He stated that the duct detectors are conventional devices with built in relays for HVAC shutdown, they are being provided by others with the HVAC units, and are only being monitored with the AIMs to give them addressable points.
1st review completed  12/1/2010 DONE
Alarm Plan Check12/1/2010 12/1/2010 PASS
DetailsStephanie L. Cobbley
Approved with redlines and review comments.
PLANS TAKEN FRONT DESK ALARM  12/1/2010 DONE
Approved redlined plans available at front counter.
Permit Ready to Issue  12/1/2010 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire12/1/2010 12/1/2010 DONE
DetailsBarbara Stitt
Telephone call  12/1/2010 DONE
DetailsBarbara Stitt
Left Ben Jackson a message that permit is ready & fees due on 12-1-10 @3:15pm
Telephone call  11/30/2010 DONE
Left a message with Jeff S. at e2co regarding concerns I have with the ceiling plan and how it will affect the ceiling mounted horn/strobes.
Application received  11/24/2010