Permit Information
Permit NumberFIR10-00608
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 729 W DIAMOND ST
Project NameVAN AUKER BLDG
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace an existing fire alarm system with new. The new system includes a full automatic detection system (to comply with City Ordinance 7-01-65 for child care facilities), a manual pull station in the riser room, sprinkler system monitoring, full notification, and HVAC monitoring/shut down.

Associated building permit: BLD10-01876 (BODIES IN MOTION - NORTH END OF BUILDING) Planning approvals under CUP10-00018 and CZC10-00168. The fire sprinkler system is used for building area increase and for fire area. To remodel a former warehouse tenant space to include a new activity center for adults and children, a café, and a daycare for children. The daycare is limited to 30 children by the conditional use permit. The 1st story will have a floor area of about 11,820 square feet. The expanded unoccupied mezzanine will have a floor area of about 2,124 square feet. A children’s play structure will be installed. Work is to include two toilet/dressing rooms accessible to the disabled, expansion of the existing unoccupied mezzanine, an exterior ramp and stairway, a unisex restroom/shower room, millwork, and interior finishes. Because it will not have a compliant egress system, the existing mezzanine and the mezzanine expansion area is not approved for any occupancy, including storage. Mezzanine expansion work includes concrete footings, wood columns, wood bearing walls, gypsum shear walls, wood beams, wood joists, and wood sheathing. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  2/9/2011 DONE
Plans taken to records for scanning.
INSP-Final Inspection1/6/20111/6/20111/6/2011PPASS
DetailsForrest France
C/N items finished. Fire alarm permit finaled.
INSP-Alarm Testing1/5/20111/6/20111/6/2011APASS
DetailsForrest France
Remainder of fire alarm work tested satisfactory.
INSP-Alarm Testing1/3/20111/4/20111/5/2011APART
DetailsForrest France
Final pending as-built drawings, correct descriptors at SD's in the restrooms, lock at the FACP breaker, knox box install, sprinkler riser testing, point map at the panel, verification of offsite monitoring and correct account information. Notification testing completed satisfactory, smoke detection at low areas tested okay.
Issue and Print Permit  12/6/2010 DONE
Plan assigned to (Stephanie)12/1/2010 12/3/2010 DONE
DetailsStephanie L. Cobbley
1st review completed  12/3/2010 DONE
Alarm Plan Check12/3/2010 12/3/2010 PASS
DetailsStephanie L. Cobbley
see review comments and redlines
PLANS TAKEN FRONT DESK ALARM  12/3/2010 DONE
Approved redlined plans available at front counter.
Permit Ready to Issue  12/3/2010 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire12/3/2010 12/3/2010 DONE
DetailsBarbara Stitt
Telephone call  12/3/2010 DONE
DetailsBarbara Stitt
Called Robert and told him that permit is ready & fees due on 12-3-10 @ 4:10pm
Case Summary  12/1/2010 DONE
DetailsBarbara Stitt
Application received  12/1/2010