Permit NumberFIR10-00610
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 9543 W EMERALD ST Unit: 104
Project NameEmerald Tilly Family Trust
Customer Number 
ePlanReviewNo
Description
Quick Permit
Add 2 new sprinklers and relocate 1 sprinklers to accommodate new wall and ceiling configuration.
The original system was calculated for Ordinary Hazard Group I. The new space is light hazard. The original flow test was S-65, R-20, Q-3000. The new flow test is S-60, R-20, Q-3000. The orignal design was .15/1650 with a demand of 305.6 Gpm @ 46.61 Psi. Since the new area is light hazard the demand would be considerably less. Therefore, no new hydraulics were required. The existing pipe sizing is 3" mains with telescoping branch lines.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/1/20113/2/20113/2/2011APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection3/1/20113/1/20113/1/2011 PASS
DetailsTroy Cobbley
Permit has been finaled
INSP-Sprinkler Rough-in12/16/201012/17/201012/17/2010PPASS
DetailsTroy Cobbley
Permit finaled
Plan assigned to (Tim)12/2/2010 12/3/2010 DONE
DetailsTim Frost
Sprinkler Plan Check12/3/2010 12/3/2010 PASS
DetailsTim Frost
Please, see attached comments.
There are NO annotations on the plans.
1st review completed  12/3/2010 DONE
DetailsTim Frost
PLANS/APPL TAKEN TO FRONT DESK  12/3/2010 DONE
DetailsTim Frost
Inspection Record Card- Fire12/3/2010 12/3/2010 DONE
DetailsDarla L Downs
Permit Ready to Issue  12/3/2010  
Telephone call  12/3/2010 DONE
12-3-10 called Ken left message permit ready ///dld
Issue and Print Permit  12/3/2010 DONE
Application received  12/2/2010  
Case Summary  12/2/2010 DONE